Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31

OSHA Accident Investigation · Summary #14392997

LIQUID AIR CORPORATION

Event
E GI V, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, INTERLOCK, LOCKOUT, SWITCHGEAR, MECH MALFUNCTION
NAICS
000000
Inspection type
Accident-driven
Activity number
#1921964
Employer profile
LIQUID AIR CORPORATION
Summary number
14392997
Report ID
625700

Event description

ELECTRIC SHOCK - CONTACT WITH ENERGIZED PARTS

Investigation abstract

Two employees were replacing a fuse in a 4160-volt starter (switchgear) for an a ir compressor. The switchgear was supplied with an interlock requiring a lever t o be pulled down to disengage the contactor unit from the bus. The interlock was designed to prevent the cabinet door from opening when the contactor unit is en gaged. It was also designed to prevent the cart to be racked in when the cabinet door is open. The interlock was broken, and one of the employees was pushing on the cart while the other employee was jiggling the lever to align the cart so i t could be racked in. The cart contacted the 4160-volt bus, electrocuting the em ployee pushing on it.

Victim

  1. #1 Fatality Age 48 M

    Nature of injury
    10
    Part of body
    4
    Event type
    12
    Source
    15
    Occupation code
    575
    Human factor
    9
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.