105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14525364

COURTAD CONSTRUCTION SYSTEMS INC

Event
ELECTRIC SCREW GUN,ELECTRICAL,CORD SET,ELECTROCUTED,E C,TEMPORARY WIRING
NAICS
000000
Inspection type
Accident-driven
Activity number
#1656271
Employer profile
COURTAD CONSTRUCTION SYSTEMS INC
Summary number
14525364
Report ID
418800

Event description

ELECTRIC SHOCK - UTILIZATION EQUIPMENT

Investigation abstract

AN EMPLOYEE WAS ENGAGED IN OPERATIONS RELATED TO SECURING SHEET ALUMINUM TO A MA THE CORD SETS. NONE OF THE RECEPTACLES WERE GFCI-PROTECTED, NOR WAS THERE AN ASS URED EQUIPMENT GROUNDING CONDUCTOR PROGRAM IN EFFECT. A CHECK OF THE TOOL AND CO RDS ALLEGED TO HAVE BEEN USED GAVE NO INDICATION OF WHAT CAUSED THE ELECTRIC SHO CK. NSARD ROOF OVERHANG OF A NEW BUILDING. HE CLIMBED A WOODEN EXTENSION LADDER TO T HE ROOF FRAMING, APPROXIMATELY 16 FEET ABOVE GROUND LEVEL. HE WAS CARRYING AN EL ECTRIC SCREW GUN IN ONE HAND AND HAD CORD SETS SLUNG OVER HIS SHOULDER. HE TURNE D SLIGHTLY AND SAID THAT HE HAD BEEN SHOCKED. THEN HE FELL TO THE GROUND, STRIKI NG A PROTRUDING SCAFFOLD PLANK ON THE WAY DOWN. HE IMMEDIATELY GOT UP, SAYING AG AIN THAT HE HAD BEEN SHOCKED, TOOK ABOUT 2 STEPS, AND FELL DOWN AGAIN. HE DIED O F ELECTROCUTION. A PERMANENT RECEPTACLE OUTLET INSTALLED IN AN EXISTING BUILDING , ABOUT 300 FEET AWAY, WAS BEING USED TO PROVIDE POWER TO THE SCREW GUN THROUGH

Victim

  1. #1 Fatality Age 19 M

    Nature of injury
    10
    Part of body
    4
    Event type
    12
    Source
    21
    Occupation code
    999
    Human factor
    1
    Environmental factor
    13
    Task assigned
    1