105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14567804

LAKE CUNNINGHAM FIRE DEPT

Event
FIREFIGHTER, SERVICE CONDUCTOR, ELECTRICAL, E GI VII, FIRE, ELECTRIC METER, GROUND FAULT, ELECTRIC SHOCK
NAICS
000000
Inspection type
Accident-driven
Activity number
#15133390
Employer profile
LAKE CUNNINGHAM FIRE DEPT
Summary number
14567804
Report ID
454520

Event description

ELECTRIC SHOCK - GROUND FAULT AT ELECTRIC METER

Investigation abstract

WHILE FIGHTING A TRAILER FIRE, TWO FIREMEN WERE RECEIVING ELECTRIC SHOCKS EVEN T HOUGH THE ELECTRIC METER HAD BEEN PULLED AND THOUGH THE FIREMEN WERE WEARING FUL L TURNOUT GEAR. THE ELECTRIC UTILITY WAS CALLED, AND THE ELECTRIC SERVICE WAS DI SCONNECTED AT THE TRANSFORMER POLE. THE NEUTRAL AND PHASE CONDUCTORS HAD BEEN FU SED TOGETHER, WHICH CAUSED THE RELATIVE VOLTAGE ON THE NEUTRAL TO RISE. THIS IN TURN HAD ENERGIZED THE METER BASE.

Victims (2)

  1. #1 Hospitalized Age 20 M

    Nature of injury
    10
    Part of body
    19
    Event type
    13
    Source
    15
    Occupation code
    417
    Human factor
    4
    Environmental factor
    17
    Hazardous substance
    8870
    Task assigned
    1
  2. #2 Hospitalized Age 19 M

    Nature of injury
    10
    Part of body
    19
    Event type
    13
    Source
    15
    Occupation code
    417
    Human factor
    4
    Environmental factor
    17
    Hazardous substance
    8870
    Task assigned