Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,913,242Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: AMERICAN CABINETRY, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of AMERICAN CABINETRY, INC. in 26 BRICKYARD RD., CRANBURY, NJ 08512 (NAICS 337110). OSHA activity number 311916738.

Watch American Cabinetry, INC. — free Get an email when a new federal OSHA severe-injury report for American Cabinetry, INC. is published. One employer, no account, unsubscribe in one click.
Site address
26 BRICKYARD RD.
City
CRANBURY
State
NJ
ZIP
08512
Mailing
P.O. BOX 368 26 BRICKYARD ROAD, CRANBURY, NJ 08512
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
SIC code (legacy)
2541
Employees
28
Ownership type
A
Industry flags
Manufacturing safety.

4 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $3000.00
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to the hazard of fire and/or explosion:
a/  American Cabinetry/Cranbury NJ Site - Dust Collection System
containing Class II
combustible wood dust:  Employees were exposed to the hazard of fire
and/or explosion
resulting from the ignition of the contents of the dust collection system
because the
system was not adequately maintained, cleaned and serviced.
1/  The dust collection system was not provided with a spark detection
system and/or
the spark detection system was not in operating condition.
2/  The dust collection system was not provided with a fire suppression
system
and/or
fire suppression system was not in operating condition.
3/  The dust collection system was not provided with a documented
inspection, testing
and maintenance program.
4/  Records relating to the dust collection system were not maintained.
Observed 11/5/08.
ABATEMENT:  Among other methods, one feasible and acceptable means of
abatement would
be to comply with the guidelines outlined in the National Fire Protection
Association (NFPA)
664 Standard for the Prevention of Fires and Explosions in Wood Processing
and Woodworking
Facilities (2007 Edition)
Reference:  National Fire Protection Association NFPA 664 (2007 Edition)
Standard for the Prevention of Fires/Explosions in Wood Processing and
Woodworking
Facilities:
Section 664 8.2.2.6.2 - Spark Detection System.
664.8.2.2.5.3 - Fire Suppression System.
664 10.2.1 and 664 10.2.2 - Inspection, Testing and Maintenance.
664 10.2 and 10.3 - Retention of required dust collection records.
Recent events (2)
  • — A (S) $3000.00
  • — Z (S) $3000.00

1910.22 A01

Serious Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $3000.00

1910.22 A02

Serious Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $3000.00

1910.307 B

Serious Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $3000.00
Recent events (2)
  • — A (S) $3000.00
  • — Z (S) $3000.00