Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HAWAIIAN ELECTRIC COMPANY INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of HAWAIIAN ELECTRIC COMPANY INC in 1133 FORT ST MALL, DOWNTOWN, HONOLULU, HI 96813 (NAICS 221121). OSHA activity number 313078768.

Watch Hawaiian Electric Company INC — free Get an email when a new federal OSHA severe-injury report for Hawaiian Electric Company INC is published. One employer, no account, unsubscribe in one click.
Site address
1133 FORT ST MALL, DOWNTOWN
City
HONOLULU
State
HI
ZIP
96813
Mailing
PO BOX 2750, HONOLULU, HI 96840
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
SIC code (legacy)
4911
Employees
4
Ownership type
A
Industry flags
Manufacturing safety.

6 citations on file for this inspection.

600002 A03

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $5000.00
HAR 12-60-2(a)(3) was violated because:
The employer assigned a crew of four employees to disconnect secondary and
primary
conductors from I-4A transformer located in V711 Kress No. 2, underground
electrical vault
which consisted of two separate compartments.  Three employees accidently
entered into I-3A
compartment of V711, which was not de-energized and failed to verify
circuit holdoff.
Evidences gathered during the accident investigation indicate that:
-  There was no marking distinguishing each compartment (e.g. I-3A or
I-4A).
-  I-3A circuit tag was illegible.
-  No switch # was found on the I-3A transformer.
-  No transformer # was found on the I-4A transformer.
-  The holdoff request #204 and downtown map given to the crew did not
include transformer
#, switch #, and physical location of I-4A transformer that the crew was
supposed to work on.
Failure of the employer to provide clearly marked work place/equipment and
appropriately
detailed work site information indirectly contributed to the accident
which resulted in two
employees receiving flash burn type injuries.
12-60-2(a)(3) states "Every employer shall provide safe work places and
practices by
elimination or reduction of existing or potential hazards.  Elimination of
existing or potential
hazards by design, process substitution, or other appropriate methods is
preferred because it
eliminates the need for further employee protection.  When elimination is
not feasible, reduction
of existing or potential hazards to acceptable levels, using methods such
as engineering or
administrative controls, isolation, or guarding, shall be promptly used.
When these methods are
inadequately reach acceptable levels, personal protective equipment shall
be provided and use."
Location:  V711 Kress No. 2 at 1133 Fort Street Mall, Downtown
Recent events (3)
  • — F (S) $5000.00
  • — I (S) $5000.00
  • — Z (S) $5000.00

1910.269 A02 I

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $5000.00
Recent events (3)
  • — F (S) $5000.00
  • — I (S) $5000.00
  • — Z (S) $5000.00

1910.269 A02 III

Deleted Serious 1 instance 4 exposed
Issued
Abate by
Recent events (2)
  • — J (S)
  • — Z (S)

1910.269 A02 IVC

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Recent events (3)
  • — F (S)
  • — I (S)
  • — Z (S)

1910.269 A02 VI

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Recent events (3)
  • — F (S)
  • — I (S)
  • — Z (S)

1910.269 C

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $5000.00
Recent events (2)
  • — J (S)
  • — Z (S) $5000.00

View HAWAIIAN ELECTRIC COMPANY INC's full OSHA safety record →

FB TITAN

PSE&G

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 313078768.