OSHA Inspection: BEYOND BROADWAY LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of BEYOND BROADWAY LLC in 5141 FRANKLIN ST, DENVER, CO 80216 (NAICS 111419). OSHA activity number 330632530.

Watch Beyond Broadway LLC — free Get an email when a new federal OSHA severe-injury report for Beyond Broadway LLC is published. One employer, no account, unsubscribe in one click.
Establishment
BEYOND BROADWAY LLC
Site address
5141 FRANKLIN ST
City
DENVER
State
CO
ZIP
80216
Mailing
5131 FRANKLIN ST, DENVER, CO 80216
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
111419
Employees
25
Ownership type
A

20 citations on file for this inspection.

1910.303 B08 I

Serious Gravity 5 8 instances 14 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1960.00 Reduced
29 CFR 1910.303(b)(8)(i): Electric equipment was not firmly secured to the surface on which it was mounted:\r\n\r\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the electrical outlet attached to the south rack in flower area C was firmly secured to the surface on which it was mounted.  The 120 volt outlet was zip tied to the rack and hanging off of the rack.  The outlet was used to power lights and the reverse osmosis unit in the south flower area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the electrical outlet attached to the south rack in flower area C was firmly secured to the surface on which it was mounted.  The 120 volt outlet was zip tied to the rack and tilted on an angle.  The outlet was used to power lights and fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(c) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the electrical outlet used to power lights and fans for flower area D was firmly secured to the surface on which it was mounted.  The 120 volt outlet was lying on the ground between flower areas C and D.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(d) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the Harvest Pro remote ballasts were firmly secured to the surface on which they were mounted.  The ballasts were hanging by metal chains over the vegetative area.  The ballasts operate at 240 volts 60 hertz and are used to power 1000 watt metal halide lamps in the first vegetative area next to the nursery.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(e) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the Harvest Pro remote ballasts were firmly secured to the surface on which they were mounted.  The ballasts were placed on a wooden platform above the flower areas.  The ballasts operate at 240 volts 60 hertz and are used to power 1000 watt high pressure sodium lamps in the flower areas.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(f) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the temporary power tap near the reverse osmosis unit was firmly secured to the surface on which it was mounted.  The 120 volt office type surge protector was hanging by the multiple flexible cords that were plugged into the unit.  The temporary power tap was used to power lights and the reverse osmosis pumps.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(g) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the temporary power tap hanging on the wall in the southwest vegetative area was firmly secured to the surface on which it was mounted.  The 120 volt office type surge protector was hanging on the wall by the flexible power cord.  The temporary power tap was used to power fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(h) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure the temporary power tap hanging from the ceiling in the nursery area was firmly secured to the surface on which it was mounted.  The 120 volt office type surge protector was hanging from the ceiling by the flexible power cord.  The temporary power tap was used to power the reverse osmosis unit and fans in the nursery area.  This condition exposed the employees to electrical shock hazards.\r\n\r\nAbatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.305 G01 IV A

Serious Gravity 5 4 instances 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:\r\n\r\n(a)  Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11,  the employer used flexible cords and/or cables as a substitute for the fixed wiring of a structure.  The employer used a temporary power tap and extensions cords near the reverse osmosis unit to power lights and the reverse osmosis pumps.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer used flexible cords and/or cables as a substitute for the fixed wiring of a structure.  The employer used a temporary power tap and extensions cords in the southwest vegetative area to power fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(c) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer used flexible cords and/or cables as a substitute for the fixed wiring of a structure.  The employer used a temporary power tap and extensions cords in the nursery area to power lights and the reverse osmosis pumps.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(d) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer used flexible cords and/or cables as a substitute for the fixed wiring of a structure.  The employer used temporary power taps and extensions cords in the nursery area to power lights.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and/or cables were attached to building surfaces:\r\n\r\n(a)  Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer attached flexible cords and/or cables to building surfaces to power lighting and power systems in the nursery, vegetative, and flower areas.  The employer used numerous extension cords and temporary power taps to power lighting and power systems.  The extension cords and temporary power taps were zip tied to the building surfaces.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A01

Serious Gravity 5 2 instances 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(1): Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation:\r\n\r\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer fastened two extension cords together by tying them together at the connection between the trimming area and the second vegetative area.  The extension cords were bent beyond their normal operating radius.  The extension cords were used to power a fluorescent light in the trimming area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer fastened two extension cords together by tying them together at the connection between the nursery and vegetative areas.  The extension cords were bent beyond their normal operating radius.  The extension cords were used to power a fluorescent lights and a radio in the trimming area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02

Serious Gravity 5 3 instances 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(2): The portable cord and plug-connected equipment and flexible cord sets were not being visually inspected before use on any shift for external defects and for evidence of possible internal damage:\r\n\r\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not visually inspect portable cord and plug-connected equipment and flexible cord sets before use on any shift for external defects and for evidence of possible internal damage.  Two extension cords were fastened together by tying them together at the connection between the trimming area and the second vegetative area.  The extension cords were bent beyond their normal operating radius.  The extension cords were used to power a fluorescent light in the trimming area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not visually inspect portable cord and plug-connected equipment and flexible cord sets before use on any shift for external defects and for evidence of possible internal damage.  Two extension cords were fastened together by tying them together at the connection between the nursery and vegetative areas.  The extension cords were bent beyond their normal operating radius.  The extension cords were used to power a fluorescent lights and a radio in the trimming area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(c) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not visually inspect portable cord and plug-connected equipment and flexible cord sets before use on any shift for external defects and for evidence of possible internal damage.  A green extension cord used to power a fluorescent light near the north wall in the nursery area had black tape wrapped around a damaged portion of the insulation near the light.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 F02

Serious Gravity 5 2 instances 14 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1960.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, and was not located and arranged so the purpose was evident:\\\\r\\\\n\\\\r\\\\n(a)  Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure each circuit breaker was legibly marked to indicate its purpose in the electrical panel box located on the east wall between flower areas C and D.  This condition exposed the employees to electrical shock hazards.\\\\r\\\\n\\\\r\\\\n(b)  Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure each circuit breaker was legibly marked to indicate its purpose in the electrical panel box located on the east side of the interior wall between the vegetative and flower areas.  This condition exposed the employees to electrical shock hazards.\\\\r\\\\n\\\\r\\\\n\r\n\r\nAbatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.305 A02 IX

Serious Gravity 5 2 instances 14 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1960.00 Reduced
29 CFR 1910.305(a)(2)(ix):  All lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard:\\r\\n\\r\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the 1000 watt metal halide lamps in the nursery area were protected from contact or breakage.  The lights were approximately 5 feet above the floor and the lamps did not have a cover to protect them from breaking.  This condition exposed the employees to electrical shock hazards.\\r\\n\\r\\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the 432 watt T5 soft lights attached to the rack in the middle of the nursery area were protected from contact or breakage.  The fluorescent lights were hung in the center of the rack on all three levels and the lamps did not have a cover to protect them from breaking.  This condition exposed the employees to electrical shock hazards.\\r\\n\\r\\n\r\n\r\nAbatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.305 A02 XI

Serious Gravity 5 6 instances 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(a)(2)(xi): Cable assemblies and flexible cords and cables were not supported in place at intervals that ensured that they would be protected from physical damage:\r\n\r\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the non-metallic shielded conductor to the electrical outlet attached to the south rack in flower area C was supported in place at intervals that ensured that it would be protected from physical damage.  The non-metallic shielded conductor was coiled and zip tied to the rack.  The outlet was used to power lights and the reverse osmosis unit in the south flower area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the non-metallic shielded conductor to the electrical outlet attached to the south rack in flower area C was supported in place at intervals that ensured that it would be protected from physical damage.  The non-metallic shielded conductor was hanging below the rack and not protected.  The outlet was used to power lights and fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(c) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the non-metallic shielded conductor to the electrical outlet used to power lights and fans for flower area D was supported in place at intervals that ensured that it would be protected from physical damage.  The non-metallic shielded conductor was lying on the ground between flower areas C and D.  The outlet was used to power lights and fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(d) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the non-metallic shielded conductors to the electrical panel box located on the east wall between flower areas C and D were supported in place at intervals that ensured that they would be protected from physical damage.  The conductors were not supported to any structure and were laying on the floor.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(e) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the non-metallic shielded conductors to the electrical boxes located in the front entrance on the north wall were supported in place at intervals that ensured that they would be protected from physical damage.  The conductors were not protected and supported.  The conductors powered equipment in the nursery area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(f) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the non-metallic shielded conductor to the outlet located on the north side rack in flower area A was supported in place at intervals that ensured that it would be protected from physical damage.  The conductor was zip tied around a portable fan and not protected.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 I

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1960.00 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering boxes, cabinets, or fittings were not protected from abrasions:\\\\r\\\\n\\\\r\\\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the conductors entering the electrical panel box located on the east wall between flower areas C and D were protected from abrasion.  The non-metallic shielded conductors entering the electrical box were not protected with a bushing or grommet.  This condition exposed the employees to electrical shock hazards.\\\\r\\\\n\\\\r\\\\n\r\n\r\nAbatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.305 G02 III

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: \r\n\r\n(a)  Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that the conductors entering the electrical panel box located on the east wall between flower areas C and D were provided with strain relief.  The non-metallic shielded conductors entering the electrical box did not have protection to prevent pull being directly transmitted to joints or terminal screws.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J01 IV

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1960.00 Reduced
29 CFR 1910.305(j)(1)(iv): Fixtures installed in a wet or damp location were not suitable for the location:\r\n\r\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the 432 watt T5 soft lights attached to the rack in the middle of the nursery area were designed for use in such locations.  The fluorescent lights were hung in the center of the rack on all three levels.  The rack had visible water damage and the lights were not enclosed.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.305 J02 IV

Serious Gravity 5 6 instances 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(j)(2)(iv): Receptacles installed in a wet or damp location were not suitable for the location:\r\n\r\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the electrical outlet attached to the south rack in flower area C was designed for use in such locations.  The outlet was used to power lights and the reverse osmosis unit in the south flower area.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the electrical outlet attached to the south rack in flower area C was designed for use in such locations.  The outlet was used to power lights and fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(c) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the electrical outlets attached to the south wall in the nursery area were designed for use in such locations.  The outlets were used to power lights and fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(d) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the electrical outlets attached to the north wall in the nursery area were designed for use in such locations.  The outlets were used to power lights and fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(e) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the electrical outlet attached to the south wall in the second vegetative area was designed for use in such locations.  The outlet was used to power lights and fans.  This condition exposed the employees to electrical shock hazards.\r\n\r\n(f) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On or before 6/10/11, the employer did not ensure that the electrical outlet attached to the north rack in flower area A was designed for use in such locations.  The outlet was used to power a portable fan.  This condition exposed the employees to electrical shock hazards.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 C02 I

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(c)(2)(i): Respirator users were not provided with the information contained in Appendix D to this section when the employer determined that any voluntary respirator use was permissible:\r\n\r\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that any employee using a respirator voluntarily was provided with the information contained in Appendix D to this section when the employer determined that any voluntary respirator use was permissible.  The employer provided tight-fitting facepiece respirators and N-95 filtering face piece respirators for voluntary use.  This condition exposed the employees to a respiratory hazard.\r\n\r\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 C02 II

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(c)(2)(ii): The employer did not establish and implement those elements of a written respiratory protection program necessary to ensure that any employee using a respirator voluntarily was medically able to use that respirator, and that the respirator was cleaned, stored, and maintained so that its use did not present a health hazard to the user:\\\\\\\\\\\\\\\\r\\\\\\\\\\\\\\\\n\\\\\\\\\\\\\\\\r\\\\\\\\\\\\\\\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that any employee using a respirator voluntarily was medically able to use the respirator, and that the respirator was cleaned, stored, and maintained properly.  The employer provided tight-fitting facepiece respirators for voluntary use and did not ensure that employees received a medical evaluation prior to initial use of the respirator.  This condition exposed the employees to a respiratory hazard.\\\\\\\\\\\\\\\\r\\\\\\\\\\\\\\\\n\\\\\\\\\\\\\\\\r\\\\\\\\\\\\\\\\n  Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 D01 III

Other-than-serious 9 instances 14 exposed
Issued
Abate by
Penalty
Initial $700.00 · Current $490.00 Reduced
29 CFR 1910.134(d)(1)(iii): The employer did not identify and evaluate the respiratory hazard(s) in the workplace:\\r\\n\\r\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product M-Pede Insecticide/Fungicide during spray applications.\\r\\n\\r\\n(b) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product PyGanic Crop Protection EC 5.0 ii during spray applications.\\r\\n\\r\\n(c) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product Pyrethrum TR during spray applications.\\r\\n\\r\\n(d) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product Avid 0.15 EC Miticide/Insecticide during spray applications.\\r\\n\\r\\n(e) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product Kontos during spray applications.\\r\\n\\r\\n(f) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product Judo Miticide/Insecticide during spray applications.\\r\\n\\r\\n(g) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product Eagle 20 EW Fungicide during spray applications.\\r\\n\\r\\n(h) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product Floramite SC during spray applications.\\r\\n\\r\\n(i) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not evaluate the respiratory hazard(s) in the workplace.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to the product Tetrasan 5 WDG during spray applications.\\r\\n\\r\\nAbatement note:  This evaluation shall include a reasonable estimate of employee exposures to respiratory hazard(s) and an identification of the contaminant\\\'s chemical state and physical form. Where the employer cannot identify or reasonably estimate the employee exposure, the employer shall consider the atmosphere to be IDLH.\\r\\n\\r\\n  Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $490
  • — Z (O) $700

1910.134 F02

Other-than-serious 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $700.00 · Current $490.00 Reduced
29 CFR 1910.134(f)(2): The employer did not ensure that employees using a tight-fitting facepiece respirator was fit tested prior to initial use of the respirator, whenever a different respirator facepiece (size, style, model or make) is used, or at least annually thereafter:\\\\r\\\\n\\\\r\\\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that employees required to use a tight-fitting facepiece respirator were fit tested prior to initial use of the respirator.  The employer requires half-face 3M 6300 respirators while spraying M-Pede and other pesticides.  This condition could result in employees wearing inappropriate respiratory protection for the situation and exposure to pesticide products.\\\\r\\\\n\\\\r\\\\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $490
  • — Z (O) $700

1910.134 G01 I A

Deleted Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $700.00 · Current $0.00 Reduced
29 CFR 1910.134(g)(1)(i)(A): The employer shall not permit respirators with tight-fitting facepieces to be worn by employees who have facial hair that comes between the sealing surface of the facepiece and the face or that interferes with valve function:\\\\r\\\\n\\\\r\\\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer allowed employees who are required to wear respirators to have facial hair.  The employer requires half-face 3M 6300 respirators while spraying M-Pede and other pesticides.  This condition potentially exposes employees to inhalation of pesticides due to poorly sealed respirators.\\\\r\\\\n\\\\r\\\\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $0
  • — Z (O) $700

1910.134 H02 I

Other-than-serious 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $700.00 · Current $490.00 Reduced
29 CFR 1910.134(h)(2)(i): All respirators were not stored to protect them from damage, contamination, dust, sunlight, extreme temperatures, excessive moisture, and damaging chemicals, and they were not packed or stored to prevent deformation of the facepiece and exhalation valve:\\\\r\\\\n\\\\r\\\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not ensure that all respirators were stored to protect them from damage, contamination, dust, sunlight, extreme temperatures, excessive moisture, and damaging chemicals.  This condition potentially exposes employees to respiratory hazards associated with using dirty and/or damaged respirators.\\\\r\\\\n\\\\r\\\\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $490
  • — Z (O) $700

1910.141 C01 I

Other-than-serious 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.141(c)(1)(i): Toilet facilities were not provided in accordance with Table J-1 of this section:\\\\\\\\r\\\\\\\\n\\\\\\\\r\\\\\\\\n(a) Beyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did provide the required minimum number of water closets according to Table J-1 of this section.  There was one functional water closet for 25 employees.  \\\\\\\\r\\\\\\\\n\\\\\\\\r\\\\\\\\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 L06

Other-than-serious 1 instance 16 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l):\\\\r\\\\n\\\\r\\\\n(b)\\\\tBeyond Broadway LLC at 5141 Franklin St. in Denver, CO: On and before 6/10/11, the employer did not certify that the forklift operators had been trained and evaluated as required by 29 CFR 1910.178(l) in the topics as outlined in 29 CFR 1910.178(l)(3):\\\\r\\\\n\\\\r\\\\nAbatement note: The certification shall include:\\\\r\\\\n\\\\r\\\\n(a)  The name of the operator;\\\\r\\\\n(b)  The date of the training;\\\\r\\\\n(c)  The date of the evaluation; and,\\\\r\\\\n(d)  The identity of the person(s) performing the training and evaluation.\\\\r\\\\n\\\\r\\\\n    Abatement note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).