Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: ROCHESTER GENERAL HOSPITAL

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ROCHESTER GENERAL HOSPITAL in 1425 PORTLAND AVENUE, ROCHESTER, NY 14621 (NAICS 622110). OSHA activity number 332429703.

Watch Rochester General Hospital — free Get an email when a new federal OSHA severe-injury report for Rochester General Hospital is published. One employer, no account, unsubscribe in one click.
Site address
1425 PORTLAND AVENUE
City
ROCHESTER
State
NY
ZIP
14621
Mailing
1425 PORTLAND AVENUE, ROCHESTER, NY 14621
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
6082
Ownership type
A

3 citations on file for this inspection.

1910.132 D01

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $6000.00 · Current $0.00 Reduced
29 CFR 1910.132(d)(1):     The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE)    a) On or about 3/1/12 in the Area E Basement; during the August 2011 test of the repaired Automatic Transfer Switch ( ATS) #4 an arc flash occurred inside the closed cabinet.  No injuries occured as a result of this incident.  On Februrary 21, 2012 during testing of repairs to the ATS #4 an arc flash occured in side the cabinet.  This event caused the closed cabinet doors to fly open and strike the employee conducting the test.  The force knocked him to the ground resulting in a laceration to his forehead.  Employee was not wearing eye or face protection.    No Abatement Certification
Recent events (3)
  • — J (S) $0
  • — C (S) $6000
  • — Z (S) $6000

1910.335 A01 V

Deleted Serious 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.335(a)(1)(v):     Employees shall wear protective equipment for the eyes or face wherever there is danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion.    a) On or about 3/1/12 in the Area E Basement; during a test of the repaired Automatic Transfer Switch #4 an arc flash occurred inside the cabinet.  This event caused the closed cabinet doors to fly open and strike the employee conducting the test.  The force knocked him to the ground resulting in a laceration to his forehead.  Employee was not wearing eye or face protection.    No Abatement Certification
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.137 B02 VIII

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $6000.00 · Current $4000.00 Reduced
29 CFR 1910.137(b)(2)(viii):     Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-5 and Table I-6.    a) On or about 3/1/12 throughout the facility; electrical protective equipment, such as but not limited to blankets, mats, sleeves excluding gloves, were last tested in 2010.     Abatement Certification
Recent events (3)
  • — J (S) $4000
  • — C (S) $6000
  • — Z (S) $6000

View ROCHESTER GENERAL HOSPITAL's full OSHA safety record →