BRONX, NY —
OSHA Inspection: AMERICAN FINISHED PRODUCTS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of AMERICAN FINISHED PRODUCTS in 2368 & 2377 HOFFMAN ST, BRONX, NY 10458 (NAICS 326199). OSHA activity number 338529639.
Where did this inspection happen?
- Establishment
- AMERICAN FINISHED PRODUCTS
- Site address
- 2368 & 2377 HOFFMAN ST
- City
- BRONX
- State
- NY
- ZIP
- 10458
- Mailing
- 2377 HOFFMAN ST., BRONX, NY 10458
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 18
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.212 A01
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $1400.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: Location: 2377 Hoffman St Bronx NY On or about 1/29/13, a) 2 lathes in the machine shop did not have guards to protect the operators from the rotating chucks.
Recent events (3)
- — F (S) $1400
- — C (S) $2000
- — Z (S) $2000
1910.219 D01
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $1400.00 Reduced
General-duty citation text
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): Location: 2368 Hoffman St Bronx NY On or about 1/29/13, a) Two compressors did not have their pulleys guarded.
Recent events (3)
- — F (S) $1400
- — C (S) $2000
- — Z (S) $2000
1910.219 E01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.219(e)(1)(i): Horizontal belts which had both runs 42 inches or less from the floor level were not fully enclosed by guards conforming to requirements specified in 29 CFR 1910.219(m) and (o): Location: 2368 Hoffman St Bronx NY On or about 1/29/13, a) Two compressors did not have their belts guarded.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $800.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Location: 2368 Hoffman St Bronx NY On or about 1/29/13, a) Surge protector power strips designed for household use were used to power heating equipment used in the extrusion process.
Recent events (3)
- — F (S) $800
- — C (S) $1200
- — Z (S) $1200
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Location: 2368 Hoffman St Bronx NY On or about 1/29/13, a) A circuit breaker panel did not have all of their breakers marked
Recent events (3)
- — F (S) $0
- — C (S) $1200
- — Z (S) $1200
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $1200.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Location: 2368 Hoffman St Bronx NY On or about 1/29/13, a) A circuit breaker panel had several unused openings.
Recent events (3)
- — F (S) $0
- — C (S) $1200
- — Z (S) $1200
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using and were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Location: 2368 Hoffman St Bronx NY On or about 1/29/13, a) An employee that was required to replace fuses in a 600 volt electrical panel that had exposed live parts was not using and was not provided with electrical protective equipment to protect his body.
Recent events (3)
- — F (S) $0
- — C (S) $2000
- — Z (S) $2000
1910.305 A02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installations rated 600 volts, nominal, or less were used for purposes other than those permitted in subparagraphs (A), (B) and (C) of this paragraph: Location: 2368 Hoffman St Bronx NY On or about 1/29/13, a) An extension cord was used to energize a refrigerator.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at AMERICAN FINISHED PRODUCTS
BRONX, NY—2013-01-29 00:00:00
AMERICAN FINISHED PRODUCTS
View AMERICAN FINISHED PRODUCTS's full OSHA safety record →
More inspections in this industry (NAICS 326199)
ERIE, PA—2026-07-14
CAPLUGS, LLC
CONNEAUT, OH—2026-07-13
CONTINENTAL STRUCTURAL PLASTICS
PETALUMA, CA—2026-07-10
LABCON NORTH AMERICA
KEEWATIN, MN—2026-07-09
111565 - TACKLE TAMER PRODUCTS INC
EAST FLAT ROCK, NC—2026-07-09
161517 - ELKAMET, INC.
More inspections in NY
MAYVILLE, NY—2026-07-16
MAYVILLE VILLAGE DPW
NEW HYDE PARK, NY—2026-07-16
NORTH HEMPSTEAD TN MICHAEL J TULLY PARK
CONESUS, NY—2026-07-16
CONESUS TN HIGHWAY DEPT
COMSTOCK, NY—2026-07-15
NYSDOCCS WASHINGTON CORRECTIONAL FACILITY
BALDWINSVILLE, NY—2026-07-15
LYSANDER TOWN HIGHWAY DEPARTMENT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338529639.