SYRACUSE, NY —
OSHA Inspection: GYPSUM WHOLESALERS INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of GYPSUM WHOLESALERS INC. in 3334 WALTERS ROAD, SYRACUSE, NY 13209 (NAICS 423310). OSHA activity number 339019242.
Where did this inspection happen?
- Establishment
- GYPSUM WHOLESALERS INC.
- Site address
- 3334 WALTERS ROAD
- City
- SYRACUSE
- State
- NY
- ZIP
- 13209
- Mailing
- 3334 WALTERS ROAD, SYRACUSE, NY 13209
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423310
- Employees
- 48
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.24 H
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $1,785 · Current $785 Reduced
General-duty citation text
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms: a) Screw Room, storage mezzanine, on or about 4/23/13: A fixed stairway to the upper storage mezzanine with five risers was not provided with a midrail on the left side descending. b) Bldg. 2, stairway to insulation mezzanine, on or about 4/23/13: A fixed stairway to the mezzanine with 14 risers was not provided with guardrails on the left side descending in that there was a 5 1/2 inch opening between the stairway and wall. Abatement certification must be submitted for these items.
Recent events (3)
- — J (O) $785
- — C (S) $1785
- — Z (S) $1785
1910.36 D01
- Issued
- May 21, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $2,975 · Current $2,101 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): Exit(s) were locked or fastened preventing free escape from inside the building: a) Screw Room, on or about 4/23/13: The exit door was locked. Abatement certification must be submitted for this item.
Recent events (3)
- — J (O) $2101
- — C (S) $2975
- — Z (S) $2975
1910.37 A03
- Issued
- May 21, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) Bldg. 2, on or about 4/23/13: Means of egress to two exit doors were blocked by pallets of material. Abatement certification must be submitted for this item.
Recent events (3)
- — J (O) $0
- — C (S) $0
- — Z (S) $0
1910.37 B04
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: a) Bldg. 2, on or about 4/23/13: There were no exit directional signs provided indicating the direction of travel to the nearest exit. Abatement certification must be submitted for this item.
Recent events (3)
- — J (O) $0
- — C (S) $0
- — Z (S) $0
1910.136 A
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $2,975 · Current $2,975
General-duty citation text
29 CFR 1910.136(a): The employer did not ensure that each affected employee uses protective footwear when working in areas where there is a danger of foot injuries due to falling or rolling objects: a) At the establishment, on or about 4/23/13: Employer did not ensure that employees in the warehouse and delivering of product wore safety toed shoes with metatarsals. Abatement certification must be submitted for this item.
Recent events (3)
- — J (S) $2975
- — C (S) $2975
- — Z (S) $2975
1910.157 G02
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $1,785 · Current $785 Reduced
General-duty citation text
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter: a) At the establishment, on or about 4/23/13: There was no training provided to employees on the use of fire extinguishers and the hazards involved with incipient stage fire fighting. Abatement certification must be submitted for this item.
Recent events (3)
- — J (O) $785
- — C (S) $1785
- — Z (S) $1785
1910.303 F02
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $2,975 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Power Room, on or about 4/23/13: A circuit breaker panel labeled Panel A did not have the breakers labeled as to what they controlled. Abatement certification must be submitted for these items.
Recent events (3)
- — J (O) $2100
- — C (S) $2975
- — Z (S) $2975
1910.303 G02 I
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Screw Room, on or about 4/23/13: Circuit breaker panel at the workbench had two blanks missing. b) Power Room, Main Electrical Service Area, on or about 4/23/13: Circuit breaker panel labeled Panel A had no inner cover, exposing live electrical parts. c) Power Room, Main Electrical Service Area, on or about 4/23/13: Circuit breaker panel labeled battery charger/lighting had two blanks missing. d) Power Room, Main Electrical Service Area, on or about 4/23/13: Circuit breaker panel labeled diesel pump had one blank missing. Abatement certification must be submitted for these items.
Recent events (3)
- — J (O) $0
- — C (S) $0
- — Z (S) $0
1910.305 B01 I
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: a) Power Room, on or about 4/23/13: Conductors feeding from a circuit breaker panel labeled Panel A were not protected from abrasion. Abatement certification must be submitted for these items.
Recent events (3)
- — J (O) $0
- — C (S) $0
- — Z (S) $0
1910.1200 E01
- Issued
- May 21, 2013
- Abate by
- Jun 23, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: a) At the establishment, on or about 4/23/13: There was no written hazard communication program for employees exposed to various products including, but not limited to propane, sheetrock, insulation, plasters, etc. Abatement certification must be submitted for this item.
Recent events (3)
- — J (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Gypsum Wholesalers INC.
View Gypsum Wholesalers INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423310)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339019242.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.