Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: PRAIRIE STATE GENERATING COMPANY, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PRAIRIE STATE GENERATING COMPANY, LLC in 3872 COUNTRY HIGHWAY 12, MARISSA, IL 62257 (NAICS 221119). OSHA activity number 339175861.

Watch Prairie State Generating Company, LLC — free Get an email when a new federal OSHA severe-injury report for Prairie State Generating Company, LLC is published. One employer, no account, unsubscribe in one click.
Site address
3872 COUNTRY HIGHWAY 12
City
MARISSA
State
IL
ZIP
62257
Mailing
3872 COUNTY HIGHWAY 12, MARISSA, IL 62257
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221119
Employees
231
Ownership type
A

4 citations on file for this inspection.

1910.38 E

Serious Gravity 5 1 instance 231 exposed
Issued
Abate by
Penalty
Initial $3060.00 · Current $3060.00
29 CFR 1910.38(e):  The employer did not designate and train a sufficient number of persons to assist in the safe and orderly emergency evacuation of employees:     Employees were exposed to possible ammonia releases due to potential accidents involving a 60,000 gallon tank of anhydrous ammonia used as part of an emission control process.    The employer did not designate and train personnel to assist in the safe and orderly emergency evacuation process.
Recent events (2)
  • — I (S) $3060
  • — Z (S) $3060

1910.165 D02

Serious Gravity 5 1 instance 231 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.165(d)(2): Tests of the reliability and adequacy of nonsupervised employee alarm systems were not made at least every two months:  Employees were exposed to ammonia releases from the emissions control system, and the company had not tested the reliability and adequacy of the alarm system in the past two months.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 C01

Other-than-serious 10 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  The employer did not identify portable fire extinguishers located in the Coal Yard Reclaim Tunnel area, exposing employees to potential thermal burn hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E03

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(e)(3): The date of the annual maintenance check of portable fire extinguishers was not recorded:  Instance a) Employees are exposed to thermal burns while working in the coal yard reclaim tunnel when one fire extinguisher annual maintenance check was not recorded   Instance b) Employees are exposed to thermal burns when a fire extinguisher in the Dry ESP #2B building did not have the annual maintenance check recorded
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View PRAIRIE STATE GENERATING COMPANY, LLC's full OSHA safety record →