OSHA Inspection: INTERNATIONAL SHIPBREAKING LIMITED, L.L.C.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of INTERNATIONAL SHIPBREAKING LIMITED, L.L.C. in 18501 RL OSTOS RD EX VESSEL WICHITA, BROWNSVILLE, TX 78521 (NAICS 423930). OSHA activity number 339249658.

Watch International Shipbreaking Limited, L.L.C. — free Get an email when a new federal OSHA severe-injury report for International Shipbreaking Limited, L.L.C. is published. One employer, no account, unsubscribe in one click.
Site address
18501 RL OSTOS RD EX VESSEL WICHITA
City
BROWNSVILLE
State
TX
ZIP
78521
Mailing
18501 RL OSTOS RD, BROWNSVILLE, TX 78521
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
100
Ownership type
A

2 citations on file for this inspection.

1910.303 B01 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $0.00 Reduced
29 CFR 1910.303(b)(1)(i): Electrical equipment was not free from recognized hazards likely to cause death or serious physical harm, in that the employer did not ensure that the electrical equipment had listing or labeling identifying the purpose for which the equipment was designed:   At this work place employees performed electrical operations at temporary electrical panels and disconnected energized 120VAC 3 Phase branch circuits attached to the panel board by in adequate strain relief devices.  Employees were exposed to electrical hazards at the following panels on the vessel's top deck:        a)    Temporary Electrical Panel #20      b)    Temporary Electrical Panel #28      c)    Temporary Electrical Panel #31
Recent events (3)
  • — R (S) $0
  • — C (S) $3500
  • — Z (S) $3500

1910.305 A02 VIII

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $0.00 Reduced
29 CFR 1910.305(a)(2)(viii): Suitable disconnecting switches or plug connectors were not installed to permit the disconnection of all ungrounded conductors of each temporary circuit. Multiwire branch circuits were not provided with a means to disconnect simultaneously all ungrounded conductors at the power outlet or panelboard where the branch circuit originated:    At this work place employees performed electrical operations at temporary electrical panels and disconnected energized 120VAC 3 Phase branch circuits labeled white, black and red from the panel board individually.  Employees were exposed to electrical hazards at the following panels on the vessel's top deck :       a) Temporary Electrical Panel #20      b) Temporary Electrical Panel #28      c) Temporary Electrical Panel #31