FENTON, MO —
OSHA Inspection: BI-STATE RUBBER, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BI-STATE RUBBER, INC. in 1611 HEADLAND DRIVE, FENTON, MO 63026 (NAICS 313320). OSHA activity number 339564445.
Where did this inspection happen?
- Establishment
- BI-STATE RUBBER, INC.
- Site address
- 1611 HEADLAND DRIVE
- City
- FENTON
- State
- MO
- ZIP
- 63026
- Mailing
- 1611 HEADLAND DRIVE, FENTON, MO 63026
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 313320
- Employees
- 22
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.178 P01
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.178(p)(1): Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been taken out of service until restored to safe operating condition(s): JOB SITE: 1611 Headland Drive, MO 63026, at this facility, in the production area, a safety check of a Clark GCX-40, Model: GCX-40, S/N: 710U-76-9308, propane operated forklift, revealed a the driver's right front light was not operational and the driver's right rear tire was badly worn and torn.
Recent events (2)
- — I (S) $0
- — Z (S) $2000
1910.303 E01 II
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Electrical equipment was used when the markings giving voltage, current, wattage, or other ratings as necessary were missing: JOB SITE: 1611 Headland Drive, Fenton, MO 63026, at this facility, located on the north wall of the production area, the electrical equipment (electrical cabinets) marking giving voltage were missing.
Recent events (2)
- — I (S) $0
- — Z (S) $2000
1910.304 B03 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in wet locations were not equipped with ground-fault circuit-interrupter protection for personnel. JOB SITE: 1611 Headland Drive, Fenton, MO 63026, at this facility, located on the administrative office, 125-volt, single-phase, 15- and 20-ampere receptacles installed in the coffee bar, men and women restroom were not equipped with ground-fault circuit-interrupter protection.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 I
- Issued
- Abate by
- Penalty
- Initial $4400.00 · Current $4200.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed: JOB SITE: 1611 Headland Drive, Fenton, MO 63026, at this facility, in the production area, an electrical outlet receptacle box located on southwest corner of the building adjacent to the Hydro Norma Press, was being used with a missing knockout cover.
Recent events (2)
- — I (S) $4200
- — Z (R) $4400
More inspections at BI-STATE RUBBER, INC.
FENTON, MO—2010-11-18 00:00:00
BI-STATE RUBBER, INC.
FENTON, MO—2010-03-04 00:00:00
BI-STATE RUBBER INC
FENTON, MO—2008-08-28 00:00:00
BI-STATE RUBBER, INC.
FENTON, MO—2004-01-06 00:00:00
BI-STATE RUBBER, INC.
FENTON, MO—1998-03-18 00:00:00
BI-STATE RUBBER, INC.
View BI-STATE RUBBER, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 313320)
DANVILLE, VA—2026-04-25
INTERTAPE INC.
GLENDALE, RI—2026-04-08
BRUIN PLASTICS COMPANY INC.
LAKEWOOD, NJ—2026-04-01
ALPHA ASSOCIATES INC.
SAGINAW, MI—2026-02-03
DURO-LAST
ATLANTA, GA—2025-08-08
KITTRICH, LLC
More inspections in MO
CLINTON, MO—2026-07-14
TORCHYLO BUILDERS, LLC.
KANSAS CITY, MO—2026-07-09
NIAGARA BOTTLING
MONETT, MO—2026-07-09
MONETT METALS INC.
PARKVILLE, MO—2026-07-08
SKY-TECH ROOFING, LLC.
SPRINGFIELD, MO—2026-07-07
D & C CONSTRUCTION, LLC.
Source