2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: FOREST SERVICE, REDMOND AIR CENTER

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of FOREST SERVICE, REDMOND AIR CENTER in PINE STREET AND HIGHWAY 20, SISTERS, OR 97759 (NAICS 924120). OSHA activity number 339781635.

Watch Forest Service, Redmond AIR Center — free Get an email when a new federal OSHA severe-injury report for Forest Service, Redmond AIR Center is published. One employer, no account, unsubscribe in one click.
Site address
PINE STREET AND HIGHWAY 20
City
SISTERS
State
OR
ZIP
97759
Mailing
1740 SE OCHOCO WAY, REDMOND, OR 97756
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
160
Ownership type
D

3 citations on file for this inspection.

1910.106 E06 I

Serious Gravity 5 1 instance 160 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors from sources such as open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat:  (a) On or about May 20, 2014 the inspection revealed that employees were potentially exposed to serious injury from a 55 gallon drum of regular gasoline that was not grounded to control static electricity. The drum was located in the fire cache outdoor storage area at the Redmond Air Center, 1740 SE Ochoco Way in Redmond, Oregon.
Recent events (1)
  • — Z (S) $0

1910.304 F01 VIII

Other-than-serious 1 instance 160 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD."  (a) On or about May 20, 2014 the inspection revealed that circuit breakers used as light switches were not appropriately listed and marked. The switches were located near the entrance door of the overflow warehouse at the Redmond Air Center, at 1740 SE Ochoco Way in Redmond, Oregon.
Recent events (1)
  • — Z (O) $0

1910.1200 F06

Other-than-serious 2 instances 160 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(f)(6): Workplace labeling. Except as provided in paragraphs (f)(7) and (f)(8) of this section, the employer shall ensure that each container of hazardous chemicals in the workplace is labeled, tagged or marked with either:  (a) On or about May 20, 2014 the inspection revealed a barrel of used oil that was not labeled to indicate the contents. The barrel was located outside the saw shed at the Redmond Air Center at 1740 SE Ochoco Way in Redmond, Oregon.   (b) On or about May 20, 2014 the inspection revealed a barrel with a mixture of used oil and fuel that was not labeled to indicate the contents. The barrel was located at the fire cache outdoor storage area at the Redmond Air Center at 1740 SE Ochoco Way in Redmond, Oregon.
Recent events (1)
  • — Z (O) $0

View FOREST SERVICE, REDMOND AIR CENTER's full OSHA safety record →