OSHA Inspection: NUVERRA ENVIRONMENTAL SOLUTIONS

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of NUVERRA ENVIRONMENTAL SOLUTIONS in 4317 STATE ROUTE 225, DIAMOND, OH 44412 (NAICS 213112). OSHA activity number 339799306.

Watch Nuverra Environmental Solutions — free Get an email when a new federal OSHA severe-injury report for Nuverra Environmental Solutions is published. One employer, no account, unsubscribe in one click.
Site address
4317 STATE ROUTE 225
City
DIAMOND
State
OH
ZIP
44412
Mailing
PO BOX 187, DIAMOND, OH 44412
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
55
Ownership type
A

3 citations on file for this inspection.

1910.106 B02 VII A

Deleted Serious Gravity 5 1 instance 29 exposed
Issued
Abate by
Penalty
Initial $3400.00 · Current $0.00 Reduced
29 CFR 1910.106(b)(2)(vii)(a): Area(s) surrounding tank(s) containing flammable liquids were not provided with adequate drainage or dikes:    The diesel fuel tank located near the DEF storage shed had no dike or drain to contain spills or leaks from the tank.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3400

1910.303 B02

Serious Gravity 1 1 instance 29 exposed
Issued
Penalty
Initial $2550.00 · Current $1785.00 Reduced
29 CFR 1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:        In the DEF storage shed, the DEF pump, an overhead light and a heater, were plugged into a multiple outlet power strip.  These devices are not approved for an industrial location.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2550

1910.305 G01 II

Serious Gravity 1 1 instance 29 exposed
Issued
Penalty
Initial $2550.00 · Current $1785.00 Reduced
29 CFR 1910.305(g)(1)(ii): Flexible cords and cables were used for purposes prohibited by subparagraphs (A) through (E) of this paragraph:      An extension cord was used as a substitute for fixed wiring and was run through a hole in the shed wall:      In the DEF storage shed, the DEF pump, an overhead light and a heater, were powered by an extension cord, which ran across the lawn from the storage shed to the office building.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2550

View NUVERRA ENVIRONMENTAL SOLUTIONS's full OSHA safety record →