2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: POWER PACKAGING, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of POWER PACKAGING, INC. in 425 S. 37TH AVE., SAINT CHARLES, IL 60174 (NAICS 326199). OSHA activity number 340104660.

Watch Power Packaging, INC. — free Get an email when a new federal OSHA severe-injury report for Power Packaging, INC. is published. One employer, no account, unsubscribe in one click.
Site address
425 S. 37TH AVE.
City
SAINT CHARLES
State
IL
ZIP
60174
Mailing
425 S. 37TH AVE., SAINT CHARLES, IL 60174
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
188
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 50 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $2800.00 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to combustible dust fire hazards while working at or near indoor cartridge filter dust collectors which returned filtered air directly back into the facility:    Outside of Blending Room 1, 2 and 3: Three indoor Donaldson Torit Downflo cartridge filter dust collectors used to collect combustible powdered drink/food mix dusts generated in Room 1, 2 and 3 exhausted back into the facility and lacked a means of fire protection.    Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903. 19(c).
Recent events (2)
  • — I (S) $2800
  • — Z (S) $4000

1910.212 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $7000.00 · Current $4700.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    Nestle Tea Line 6: The employer did not ensure that the Nestle Tea Labeler on line 6 was adequately guarded in that, an employee was able to open the guard while the machine was still running to line containers and/or repair labels, exposing the employee to a fracture or caught in hazard.    Documentation required for this item in accordance with the requirements of 29 CFR 1910. 1903.19(d).
Recent events (2)
  • — I (S) $4700
  • — Z (S) $7000

1910.303 G01 II

Other-than-serious 1 instance 20 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $500.00 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    Lines 4, 5, 6: The working space around the circuit breaker panels was obstructed with cardboard boxes, exposing employees to the hazards associated with not being able to turn off the power in an emergency, and the employer did not ensure the required working space around electrical equipment was maintained.    Certification required for this item in accordance with the requirements of 29 CFR 1910. 1903.19(c).
Recent events (2)
  • — I (O) $500
  • — Z (S) $3000