Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,913,242Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: TRANSTAR INTERNATIONAL, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TRANSTAR INTERNATIONAL, INC. in 875 E. DEVON AVE., ELK GROVE VILLAGE, IL 60007 (NAICS 484110). OSHA activity number 340178391.

Watch Transtar International, INC. — free Get an email when a new federal OSHA severe-injury report for Transtar International, INC. is published. One employer, no account, unsubscribe in one click.
Site address
875 E. DEVON AVE.
City
ELK GROVE VILLAGE
State
IL
ZIP
60007
Mailing
P.O BOX 66039, ELK GROVE VILLAGE, IL 60007
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
484110
Employees
67
Ownership type
A

2 citations on file for this inspection.

1910.37 B06

Serious Gravity 1 2 instances 47 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $2100.00 Reduced
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:    Employees in the warehouse were exposed to smoke inhalation hazards due to the following emergency door exit signs not being lit:    a) The southwest emergency door exit sign.     b) The northwest emergency door exit sign.    Certification is required for this items in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3000

1910.106 E02 II B 2

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $3500.00 Reduced
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons:    Warehouse: The employer was storing an excess of 120 gallon of flammable liquids, such as, but not limited to, Rinse, Developer, SermaGard, and Betaseal inside the warehouse outside a flammable room or storage cabinet which created a fire and/or explosion hazard.    Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
  • — I (S) $3500
  • — Z (S) $5000

View TRANSTAR INTERNATIONAL, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340178391.