Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: ROCHESTER OVERNIGHT PLATING LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ROCHESTER OVERNIGHT PLATING LLC in 2 CARIN STREET, ROCHESTER, NY 14611 (NAICS 332813). OSHA activity number 340207315.

Watch Rochester Overnight Plating LLC — free Get an email when a new federal OSHA severe-injury report for Rochester Overnight Plating LLC is published. One employer, no account, unsubscribe in one click.
Site address
2 CARIN STREET
City
ROCHESTER
State
NY
ZIP
14611
Mailing
2 CARIN STREET, ROCHESTER, NY 14611
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332813
Employees
33
Ownership type
A

7 citations on file for this inspection.

1910.151 C

Serious Gravity 5 3 instances 6 exposed
Issued
Penalty
Initial $2023.00 · Current $1648.00 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided for immediate emergency use:     a) On or about 01/22/15 in the Nickel line; employer failed to protect employees against a more serious chemical burn when they allowed the eye wash station in the north west corner to be blocked with two 15 gallon containers and allowed a graduated cylinder to be placed inside the eye wash bowl.     b) On or about 01/22/15 at Line #2; employer failed to protect employees against struck by hazards when they allowed the eye wash station bowl, on the north portion of the tanks, to be used as a storage rack for the compressed air gun and a thermometer.      c) On or about 01/22/15 at Line #1; employer failed to protect employees against struck by hazards when they allowed the eye wash station bowl, on the north portion of the tanks, to be used as a storage rack for the compressed air gun and gloves.      ABATEMENT CERTIFICAITON REQURIED
Recent events (2)
  • — I (S) $1648
  • — Z (S) $2023

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2352.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) On or about 01/23/15 in the Nickel line; employer failed to protect employees from contact with electrical current when the Hubbell brand Circuit Guard portable ground fault circuit interrupter ( issue number B-237364) was plugged into a cord and plug connection on the portable platting barrel which was missing a grounding pin, while the label on the female end of the Circuit Guard device stated " use this product with a 3 conductor 120 V 15 A cord set."        ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $2352
  • — Z (S) $2800

1910.334 A02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  a) On or about 01/23/15 in the Nickel line; employer failed to protect employees from contact with electrical current when the cord and plug connection for the portable platting barrel was missing a grounding pin.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $2500.00 Reduced
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity:    a) On or about 01/23/15 at the north east side of Line #2 on the ground level; employer failed to protect employees against contact with electrical current when the outlet used to plug in the temperature probe for the clear chromate color tank had the hot and neutral conductors reversed.      ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $2500
  • — Z (S) $3500

1910.304 G05

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not effective:  a) On or about 01/23/15 at the north east side of Line #2 on the ground level; employer failed to protect employees against contact with electrical current when the outlet used to plug in the temperature probe for the clear chromate color tank had a bad ground.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Repeat Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $8400.00 · Current $2000.00 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:    (a) On or about 01/23/15 in throughout the facility; employer failed to protect employees against contact with electrical current when they did not enforce the use of protective equipment during work such as but not limited to, conducting voltage testing (240/480 volts AC), removing fuses.     ABATEMENT DOCUMENTATION REQUIRED    Rochester Overnight Plating was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.335 (a) (1) (i) which was contained in OSHA inspection number 315095786, citation number  01, item number 004 and was affirmed as a final order on 02/09/11, with respect to a workplace located at2 Carin Street, Rochester, New York, 14611.
Recent events (2)
  • — I (R) $2000
  • — Z (R) $8400

1910.179 G01 V

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.179(g)(1)(v): Pendant control box(es) were not clearly marked for identification of functions:  a) On or about 01/22/15 in the Line #2 area; employer failed to protect employees against contact with corrosive liquids when the push buttons on the pendant control box for the overhead crane were not legible.  This condition could create an incorrect action by the crane operator causing the parts rack to fall into the tank resulting in a splash of corrosive liquids.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View ROCHESTER OVERNIGHT PLATING LLC's full OSHA safety record →