OSHA Inspection: USDA-RURAL DEVELOPMENT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of USDA-RURAL DEVELOPMENT in CARIBBEAN CINEMA COURT BLDG CARRETERA #2 ESQUINA CARR #122, KM 174, SAN GERMAN, PR 00683 (NAICS 925120). OSHA activity number 340514116.

Watch Usda-Rural Development — free Get an email when a new federal OSHA severe-injury report for Usda-Rural Development is published. One employer, no account, unsubscribe in one click.
Site address
CARIBBEAN CINEMA COURT BLDG CARRETERA #2 ESQUINA CARR #122, KM 174
City
SAN GERMAN
State
PR
ZIP
00683
Mailing
CARIBBEAN CINEMA COURT BLDG CARRETERA #2 ESQUINA CARR #122, KM 174, SAN GERMAN, PR 00683
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
925120
Employees
5
Ownership type
D

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 4 instances 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:    a) On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the computer room, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  b) On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the Specialist work area #3, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.  c) On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the Specialist work area #1, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.  d) On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the Specialist work area #5, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.303 F02

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident:    On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the conference room, the circuit breakers or fuses in the electrical panel were not identified or labeled to show the locations of the building whose circuits it protects.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the conference room, an electrical outlet box was not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury:  On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the storage room, a portable fire extinguisher was not mounted.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (O) $0

1910.157 E03

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On or about 03/06/15, at the Caribbean Cinema Court Building, San Sebastian, PR, in the Specialist work area #4, a portable fire extinguisher was not maintained annually.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.