Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,913,242Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: AMERICAN COMPOST CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AMERICAN COMPOST CORPORATION in 2022 MOUNTAIN ROAD, MANHEIM, PA 17545 (NAICS 325311). OSHA activity number 341331817.

Watch American Compost Corporation — free Get an email when a new federal OSHA severe-injury report for American Compost Corporation is published. One employer, no account, unsubscribe in one click.
Site address
2022 MOUNTAIN ROAD
City
MANHEIM
State
PA
ZIP
17545
Mailing
320 GODSHALL DRIVE, HARLEYSVILLE, PA 19438
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325311
Employees
155
Ownership type
A

3 citations on file for this inspection.

1910.303 B07 IV

Serious Gravity 10 1 instance 3 exposed
Issued
Penalty
Initial $6300.00 · Current $250.00 Reduced
29 CFR 1910.303(b)(7)(iv): Equipment with damaged parts that may adversely affect its safe operation or its mechanical strength, such as broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating parts shall not be used:     2022 Mountain Road - Employees were exposed to electrical shock or burns where the electrical cabinet operating at 480v was in use with a bent right door and broken latch.  The box could not be closed thereby, exposing employees to potential electrical shocks and/or burns on or about March 17, 2016.    No abatement certification or documentation required.
Recent events (3)
  • — F (S) $250
  • — C (S) $6300
  • — Z (S) $6300

1910.303 E

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(e): Markings were not provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary:  a) 2022 Mountain road - The 480v panel located in the production floor had no markings to identify the voltage, its purpose and other markings required by the manufacturer, thereby exposing employees to hazardous energy shocks, burns or electrocution on or about March 17, 2016.   No abatement certification or documentation required.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $4500.00 · Current $250.00 Reduced
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasions:    a) 2022 Mountain Road -The flexible cable leading into to the panel was missing approximately 3 inches of protective sheathing and was not protected from abrasions, thereby exposing employees to shock or electrocution hazards to employees who have access to the 480v panel.     No abatement certification or documentation required.
Recent events (3)
  • — F (S) $250
  • — C (S) $4500
  • — Z (S) $4500