Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: WEST POINT DAIRY PRODUCTS, LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of WEST POINT DAIRY PRODUCTS, LLC in 1715 E ROAD, WEST POINT, NE 68788 (NAICS 311512). OSHA activity number 341754679.

Watch West Point Dairy Products, LLC — free Get an email when a new federal OSHA severe-injury report for West Point Dairy Products, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1715 E ROAD
City
WEST POINT
State
NE
ZIP
68788
Mailing
1715 E ROAD, WEST POINT, NE 68788
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311512
Employees
117
Ownership type
A

4 citations on file for this inspection.

1910.119 D02 I D

Serious Gravity 5 6 instances 113 exposed
Issued
Abate by
Penalty
Initial $7696.00 · Current $5388.00 Reduced

Hazardous substances 0170

29 CFR 1910.119(d)(2)(i)(D): Information concerning the technology of the process did not include safe upper and lower limits for such items as temperatures, pressures, flows or compositions:    Employer is not ensuring that nameplates/data tags on pressure vessels including, but not limited to Silos #1,#2, and #19 are labeled/stamped with a minimum design metal temperature (MDMT). This violation was last observed on or about September 23, 2016.
Recent events (2)
  • — I (S) $5388
  • — Z (S) $7696

1910.119 D03 II

Serious Gravity 5 3 instances 25 exposed
Issued
Penalty
Initial $7696.00 · Current $5388.00 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices:     Instance a)  On or about September 22, 2016, at the West Point Dairy Products, LLC, facility, the employer did not document that it complied with recognized and generally accepted good engineering practice (RAGAGEP), such as ASHRAE 15 (2013), Section 8.13(f), when it did not ensure that three south wall penetrations for piping and conduit were sealed to prevent ammonia from communicating from the ammonia engine/compressor room to occupied spaces, exposing employees to the hazards of inhalation of toxic ammonia and ammonia burns.
Recent events (2)
  • — I (S) $5388
  • — Z (S) $7696

1910.119 J04 I

Serious Gravity 5 9 instances 113 exposed
Issued
Abate by
Penalty
Initial $7696.00 · Current $5388.00 Reduced

Hazardous substances 0170

29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment.    On or about September 22, 2016, at the West Point Dairy Products, LLC facility, the employer did not ensure that the inspection and /or testing of the High Pressure Receiver and associated piping was of a frequency to prevent rust, corrosion, bubbled paint that contained water, and an illegible data plate.
Recent events (2)
  • — I (S) $5388
  • — Z (S) $7696

1910.119 O04

Serious Gravity 5 15 instances 113 exposed
Issued
Abate by
Penalty
Initial $7696.00 · Current $5386.00 Reduced

Hazardous substances 0170

29 CFR 1910.119(o)(4): The employer did not correct deficiencies identified during a compliance audit in a timely manner.    On or about November 3, 2016, at the West Point Dairy Products, LLC, facility the employer is failing to correct the following deficiencies/instances from the April 6, 2013 Mechanical Integrity Inspection / Compliance Audit in a timely manner:    A) Pressure relief capacity for surge drum SD-S-1 is not sized for the capacity of the surge drum plus connected Silo #1.   B) Pressure relief capacity for surge drum SD-S-2 is not sized for the capacity of the surge drum plus connected Silo #2.  C) Pressure relief capacity for surge drum SD-S-3 is not sized for the capacity of the surge drum plus connected Silo #3.  D) Pressure relief capacity for surge drum SD-S-4 is not sized for the capacity of the surge drum plus connected Silo #4.  E) Pressure relief capacity for surge drum SD-S-5 is not sized for the capacity of the surge drum plus connected Silo #5.  F) Pressure relief capacity for surge drum SD-S-6 is not sized for the capacity of the surge drum plus connected Silo #6.  G) Pressure relief capacity for surge drum SD-S-7 is not sized for the capacity of the surge drum plus connected Silo #7.  H) Pressure relief capacity for surge drum SD-S-8 is not sized for the capacity of the surge drum plus connected Silo #8.  I) Pressure relief capacity for surge drum SD-S-9 is not sized for the capacity of the surge drum plus connected Silo #9.  J) Pressure relief capacity for surge drum SD-S-11 is not sized for the capacity of the surge drum plus connected Silo #11.  K) Pressure relief capacity for surge drum SD-S-12 is not sized for the capacity of the surge drum plus connected Silo #12.  L) Pressure relief capacity for surge drum SD-S-13 is not sized for the capacity of the surge drum plus connected Silo #13.  M) Pressure relief capacity for surge drum SD-S-14 is not sized for the capacity of the surge drum plus connected Silo #14.  N) Pressure relief capacity for surge drum SD-S-16 is not sized for the capacity of the surge drum plus connected Silo #16.  O) Pressure relief capacity for surge drum SD-S-17 is not sized for the capacity of the surge drum plus connected Silo #17.  P) Pressure relief capacity for surge drum SD-S-19 is not sized for the capacity of the surge drum plus connected Silo #19.  Q)Pressure relief capacity for surge drum SD-S-21 is not sized for the capacity of the surge drum plus connected Silo #21.
Recent events (2)
  • — I (S) $5386
  • — Z (S) $7696

View WEST POINT DAIRY PRODUCTS, LLC's full OSHA safety record →