FORT STOCKTON, TX —
OSHA Inspection: JW POWERLINE
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of JW POWERLINE in 5697 TRANS PECOS RD., FORT STOCKTON, TX 79735 (NAICS 238210). OSHA activity number 342041621.
Where did this inspection happen?
- Establishment
- JW POWERLINE
- Site address
- 5697 TRANS PECOS RD.
- City
- FORT STOCKTON
- State
- TX
- ZIP
- 79735
- Mailing
- 700 S. FAIRGROUNDS RD., MIDLAND, TX 79701
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 135
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.269 A03 II A
- Issued
- Abate by
- Penalty
- Initial $6926.00 · Current $4000.00 Reduced
General-duty citation text
29 CFR 1910.269(a)(3)(ii)(A): The contract employer did not ensure that each of its employees was instructed in the hazardous conditions relevant to the employee's work: At the substation: On or about January 19, 2017, The contract employer did not ensure that each of its employees was instructed in the hazardous conditions relevant to the employee's work. Employees were exposed to electrical shock hazards.
Recent events (3)
- — F (S) $4000
- — C (S) $6926
- — Z (S) $6926
1910.333 A01
- Issued
- Abate by
- Penalty
- Initial $6926.00 · Current $4000.00 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): The employer failed to ensure that live parts were de-energized before employees began to work on or near live parts. At the substation: On or about January 19, 2017, at the substation; the employer did not ensure that live parts were de-energized before allowing employees to work on or near live parts. Employees were exposed to electrical shock hazards.
Recent events (3)
- — F (S) $4000
- — C (S) $6926
- — Z (S) $6926
1910.333 B02 I
- Issued
- Abate by
- Penalty
- Initial $6926.00 · Current $4000.00 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: At the substation: On or about January 19, 2017, the employer did not provided OSHA rep with a written copy of the procedures as outlined in 29 CFR 1910.333(b)(2).
Recent events (3)
- — F (S) $4000
- — C (S) $6926
- — Z (S) $6926
1910.333 B02 II B
- Issued
- Abate by
- Penalty
- Initial $6926.00 · Current $4000.00 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(B): Control circuit devices, such as push buttons, selector switches, and interlocks, were used as the sole means for de-energizing circuits and equipment: At the substation: On or about January 19, 2017, the employer relied on the use of a selector switch as thee sole means for de-energizing VISTA distribution switchgear. The VISTA distribution switchgear was de-energized on the out-going side, but remained energized on the in-coming side.Employees were exposed to electrical hazards.
Recent events (3)
- — F (S) $4000
- — C (S) $6926
- — Z (S) $6926
1910.333 B02 IV
- Issued
- Abate by
- Penalty
- Initial $6926.00 · Current $4000.00 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(iv): The employer did not properly verify if the components were positively de-energized or in an otherwise safe condition to protect the employees from an electrical shock hazard. At the substation: On or about January 19, 2017, the employer did not verify equipment was positively de-energized. Employees were exposed to electrical shock hazards.
Recent events (3)
- — F (S) $4000
- — C (S) $6926
- — Z (S) $6926
More inspections in this industry (NAICS 238210)
SOUTH FULTON, GA—2026-07-10
REEDWICK, LLC
NIAGARA FALLS, NY—2026-07-10
GAINES ELECTRICAL CONTRACTING, INC.
OGDENSBURG, NY—2026-07-10
S & L ELECTRIC, INC.
BOISE, ID—2026-07-09
POWERHOUSE ELECTRIC INC.
LYNCHBURG, VA—2026-07-09
WHITE ELECTRICAL SERVICES LLC
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342041621.