Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SHERMCO INDUSTRIES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SHERMCO INDUSTRIES, INC. in 12100 SAMSUNG BLVD., CUB 2 BLDG, AUSTIN, TX 78754 (NAICS 541380). OSHA activity number 342964830.

Watch Shermco Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Shermco Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
12100 SAMSUNG BLVD., CUB 2 BLDG
City
AUSTIN
State
TX
ZIP
78754
Mailing
1705 HUR INDUSTRIAL BLVD., CEDAR PARK, TX 78613
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541380
Employees
3
Ownership type
A

4 citations on file for this inspection.

1910.305 B03 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $12934.00 · Current $0.00 Reduced
29 CFR 1910.305(b)(3)(i): Pull and junction boxes used on systems rated over 600 volts, nominal, did not provide a complete enclosure for the contained conductors or cables  On or about February 15, 2018, and in times prior thereto, the side panel covers were missing from adjoining Ampgard, 4160 Volt electrical starter cabinets, exposing workers to the hazard of an arc flash, located in the Cub 2 Building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $12934

1910.335 A01 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  On or about February 15, 2018, and in times prior thereto, electricians were wearing short sleeve cotton shirts with no hand and arm protection while working within one inch of 4160 volts of electricity in adjacent boxes with exposed live parts.  The close proximity to live buss bars exposed the electricians to an arc flash hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $12934.00 · Current $12934.00
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized.  The specific safety-related wok practices shall be consistent with the nature and extent of the associated electrical hazards:  On or about February 15, 2018, electricians working near an energized buss did not employ appropriate safety electrical work practices in accordance with this section, exposing employees to the hazards of electrical shock and/or arc flash.
Recent events (2)
  • — I (O) $12934
  • — Z (S) $12934

1910.335 A02 II

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur.   On or about February 15, 2018, and in times prior thereto, where side panel covers were missing from adjoining Ampgard, 4160 Volt electrical starter cabinets, and no temporary shields or barriers were used to isolate from live parts and arc flash hazards, exposing workers to the hazard of an arc flash, located in the Cub 2 Building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View SHERMCO INDUSTRIES, INC.'s full OSHA safety record →