OSHA Inspection: LONDONDERRY FREEZER WAREHOUSE, LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of LONDONDERRY FREEZER WAREHOUSE, LLC in 219 ROCKINGHAM ROAD, LONDONDERRY, NH 03053 (NAICS 493120). OSHA activity number 343023628.

Watch Londonderry Freezer Warehouse, LLC — free Get an email when a new federal OSHA severe-injury report for Londonderry Freezer Warehouse, LLC is published. One employer, no account, unsubscribe in one click.
Site address
219 ROCKINGHAM ROAD
City
LONDONDERRY
State
NH
ZIP
03053
Mailing
219 ROCKINGHAM ROAD, LONDONDERRY, NH 03053
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
20
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 9 instances 20 exposed
Issued
Abate by
Penalty
Initial $3696.00 · Current $1848.00 Reduced

Hazardous substances 0170

OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish the employees employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to chemical burns and inhalation hazards from an uncontrolled release of anhydrous ammonia:  a. South Engine Room - On or about March 15, 2018, the ammonia piping mains, headers and branches were not marked ammonia and identified as to the physical state of the refrigerant, the relative pressure level of the refrigerant, and the direction of flow.  Reference:  IIAR 2-2014, Section 5.14.5.    b. North Engine Room - On or about March 15, 2018, the ammonia system king valve (NV1 008) was not clearly and uniquely identified as an emergency shutdown valve.  Reference:  IIAR 2-2014, Section 5.14.3.    c. South Engine Room - On or about March 15, 2018, the +15 degree F Intercooler oil pot (S-OP-1) nameplate did not provide the manufacturer's information and design limits and purpose.  Reference:  IIAR 2-2014, Section 5.14.4.1.    d. South Engine Room - On or about March 15, 2018, the ammonia system king valve (S3V 007) was not directly operable or chain-operated from the work surface.  The king valve was located approximately 82 inches (6 feet, 10 inches) above the floor.  Reference:  IIAR 2-2014, Section 6.3.3.2.    e. North Engine Room - On or about March 15, 2018, the ammonia system king valve (NV1 008) was not directly operable or chain-operated from the work surface.  The king valve was located approximately 96 inches (8 feet) above the floor.  Reference:  IIAR 2-2014, Section 6.3.3.2.    f. South Rooftop Evaporative Condenser System - On or about March 15, 2018, the ammonia relief vent discharge was 68 inches (5 feet, 8 inches) above the highest platform accessed by employees during service and inspection.  Reference:  IIAR 2-2014, Section 15.5.1.4.    g. North Rooftop Evaporative Condenser System - On or about March 15, 2018, the ammonia relief vent discharge was located below the highest platform accessed by employees during service and inspection.  Reference:  IIAR 2-2014, Section 15.5.1.4.    h. South Rooftop Evaporative Condenser System - On or about March 15, 2018, the termination of the ammonia relief vent discharge was directed downward and not arranged to avoid spraying ammonia on to employees in the vicinity during service and inspection.  Reference:  IIAR 2-2014, Section 15.5.1.5.    i. North Rooftop Evaporative Condenser System - On or about March 15, 2018, the termination of the ammonia relief vent discharge was directed downward and not arranged to avoid spraying ammonia on to employees in the vicinity during service and inspection.  Reference:  IIAR 2-2014, Section 15.5.1.5.
Recent events (2)
  • — I (S) $1848
  • — Z (S) $3696

1910.303 G02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3696.00 · Current $1848.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    Near the south rooftop condenser unit - On or about April 14, 2018, employees were exposed to live parts of a combination junction box and electrical outlet.