STONINGTON, IL —
OSHA Inspection: SHELBY ELECTRIC COOPERATIVE
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SHELBY ELECTRIC COOPERATIVE in 2200 N ROAD, STONINGTON, IL 62567 (NAICS 221122). OSHA activity number 343488417.
Where did this inspection happen?
- Establishment
- SHELBY ELECTRIC COOPERATIVE
- Site address
- 2200 N ROAD
- City
- STONINGTON
- State
- IL
- ZIP
- 62567
- Mailing
- 1355 STATE HWY 128, SHELBYVILLE, IL 62565
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 53
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.269 L03 III A
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $6150.00 Reduced
General-duty citation text
29 CFR 1910.269(l)(3)(iii)(A): The employee was not insulated from the energized part (rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (l)(4) of this section constitutes insulation of the employee from the energized part upon which the employee is working provided that the employee has control of the part in a manner sufficient to prevent exposure to uninsulated portions of the employee's body). On or about September 20, 2018, an employee performing repair activities on a downed transmission line was exposed to electrical hazards and the employer did not ensure that the employee was insulated from the energized part.
Recent events (2)
- — I (S) $6150
- — Z (S) $9282
1910.269 M03 II
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $6150.00 Reduced
General-duty citation text
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy might be supplied to the particular lines and equipment were de-energized / inoperable (i.e. open): On or about September 20, 2018, employees performing repair activities on a downed transmission line were exposed to electrical hazards and the employer did not ensure that all switches, disconnectors, jumpers, taps and other means through which known sources of electrical energy might be supplied to the downed line were de-energized/inoperable.
Recent events (2)
- — I (S) $6150
- — Z (S) $9282
1910.269 N02
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $6200.00 Reduced
General-duty citation text
29 CFR 1910.269(n)(2): For any employee to work transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section: On or about September 20, 2018, employees performing repair activities on a downed transmission line were exposed to electrical hazards and the employer did not ensure the line was properly grounded.
Recent events (2)
- — I (S) $6200
- — Z (S) $9282
1910.269 N05
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(n)(5): The employer did not ensure employees tested line and equipment to verify the absence of nominal voltage before installing grounds when previously installed grounds were not present. On or about September 20, 2018, employees performing repair activities on a downed transmission line were exposed to electrical hazards and the employer did not ensure the line was tested to verify the absence of nominal voltage before installing ground(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 221122)
LITTLETON, MA—2026-07-01
LITTLETON ELECTRIC LIGHT & WATER DEPARTMENT
PISCATAWAY, NJ—2026-06-30
PSE&G
BAYTOWN, TX—2026-06-30
CENTERPOINT ENERGY
SACRAMENTO, CA—2026-06-29
SACRAMENTO MUNICIPAL UTILITY DISTRICT
PHILADELPHIA, PA—2026-06-25
PECO ENERGY COMPANY
More inspections in IL
BLOOMINGTON, IL—2026-07-13
UNKNOWN CONTRACTOR