OSHA Inspection: BIG LOTS , INC #1762

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BIG LOTS , INC #1762 in 698 S OGDEN ST, CHEEKTOWAGA, NY 14206 (NAICS 452990). OSHA activity number 343636437.

Watch BIG Lots , INC #1762 — free Get an email when a new federal OSHA severe-injury report for BIG Lots , INC #1762 is published. One employer, no account, unsubscribe in one click.
Site address
698 S OGDEN ST
City
CHEEKTOWAGA
State
NY
ZIP
14206
Mailing
4900 EAST DUBLIN GRANVILLE RD., WESTERVILLE, OH 43081
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
452990
Employees
23
Ownership type
A

3 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 1 instance 23 exposed
Issued
Abate by
Penalty
Initial $5543.00 · Current $5000.00 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:    a) On or about 11/29/18, in the Fixture Room, employees were exposed to fire and electrical hazards when entering the fixture room due to an outlet, located at the left wall of the entrance, without a faceplate and exposed live electrical wiring.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5543

1910.303 F02

Other-than-serious 1 instance 23 exposed
Issued
Abate by
Penalty
Initial $5543.00 · Current $2000.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    a) On or about 11/29/18, in the Fixture Room, each circuit breaker in the electrical panel (PP-1) was not legibly marked to indicate its purpose.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (O) $2000
  • — Z (S) $5543

1910.303 G01

Serious Gravity 1 1 instance 23 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a) On or about 11/29/18, in the fixture room, electrical panel (PP-1) did not have sufficient space to permit ready and safe operation and maintenance of electrical panel exposing employees to electrical hazards in case of emergency.  NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View BIG LOTS , INC #1762's full OSHA safety record →