OSHA Inspection: BEST PRESS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BEST PRESS, INC. in 4201 AIRBORN DR., ADDISON, TX 75001 (NAICS 323111). OSHA activity number 343728549.

Watch Best Press, INC. — free Get an email when a new federal OSHA severe-injury report for Best Press, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
BEST PRESS, INC.
Site address
4201 AIRBORN DR.
City
ADDISON
State
TX
ZIP
75001
Mailing
4201 AIRBORN DR., ADDISON, TX 75001
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323111
Employees
70
Ownership type
A

12 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 3 instances 5 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $3315.00 Reduced
29 CFR 1910.22(a)(1): (1) All places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition:    a) The employer did not ensure that all places of employment, and passageways were kept clean and orderly and in a sanitary condition.  This violation was observed on or about January 16, 2019, and at times after thereto; when passageways/working areas were not keep clear from electrical cords, and air lines, exposing employees to trip and fall hazards:    a.   In the Finishing department,  automatic punch machine area.  b.   In the Finishing department, mail room area.  c.   In the Maintenance shop area.
Recent events (2)
  • — I (S) $3315
  • — Z (S) $6630

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $0.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) The employer did not ensure electrical equipment  is used and installed in accordance with the listing or labeling instructions.  This violation occurred on or about January 23, 2019 and at times prior thereto; in the finishing department, mail room area, a relocatable power tap/power strip was being used to provide power to TABBER machine and fan.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6630

1910.157 C04

Other-than-serious 2 instances 7 exposed
Issued
Abate by
Penalty
Initial $3978.00 · Current $1989.00 Reduced
29 CFR 1910.157(c)(4): Portable fire extinguishers were not kept in their designated places at all times except during use:    a)  On or about January 16, 2019, and at times after thereto, portable fire extinguishers were not kept in their designated places:    a.  In the Press department, pump room area.  b.  In the Maintenance shop.
Recent events (2)
  • — I (O) $1989
  • — Z (S) $3978

1910.212 A05

Deleted Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $3978.00 · Current $0.00 Reduced
29 CFR 1910.212(a)(5): Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch:  a)  In the mail room area, Lasiko fan in use had openings in the fan blade guard larger than one half inch.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3978

1910.213 D01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $3315.00 Reduced
29 CFR 1910.213(d)(1): Circular handfed crosscut table saw(s) were not guarded by an automatically adjusting hood which completely enclosed that portion of the saw above the table and above the material being cut:    a) On or about March 6, 2019, and at times prior thereto; In the Maintenance shop, where employees used table saw without guard.
Recent events (2)
  • — I (S) $3315
  • — Z (S) $6630

1910.304 G05

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $0.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    a) In the Maintenance shop, where employees were exposed to electrical hazards while using Delta table saw that missing ground.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6630

1910.303 E01 II

Serious Gravity 5 6 instances 12 exposed
Issued
Abate by
Penalty
Initial $5304.00 · Current $2652.00 Reduced
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary:    a)  On or about January 23, 2019, and at times prior thereto; the circuit breaker panels were used without markings giving voltage, current, wattage, or other ratings as necessary.        a.  In the Press department, panel N/pressroom S3      b.  In the press department , panel HE4        c.  In the Finishing department, panel AB/pressroom NE1  d.  In the Finishing department, panel HE1  e.  In the Finishing department, panel HE2  f.  In the Finishing department, bindrey area, panel E1
Recent events (2)
  • — I (S) $2652
  • — Z (S) $5304

1910.305 B01 I

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $3315.00 Reduced
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:    a) This violation was observed on or about January 16, 2019; in the Finishing department, where openings through which conductors entered the Spectra Series Power Panel Board, 480-volt, 3-phase, 4-wire, 400A, were not effectively closed, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $3315
  • — Z (S) $6630

1910.305 B01 II

Serious Gravity 5 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $0.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    a) The employer did not close unused openings on electrical equipment.  This violation occurred on or about January 16, 2019, and at times after thereto:    a.   In the Press department, electrical panel "press room S2" had openings of 1/4-inch at circuit breakers #7, #8, #13, and #14.    b.   In the Finishing department, two (2) circuit breakers were missing from the Spectra Series power panel board.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6630

1910.305 G01 IV A

Other-than-serious 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $3315.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a) The employer did not ensure that flexible cords and cables were not used as a substitute for the fixed wiring of a structure.    a. This violation occurred on or about January 23, 2019 and at times prior thereto; in the finishing department, mail room area, where flexible cord was used as a substitute for the fixed wiring of a structure.    b. This violation occurred on or about March 6, 2019, and at times prior thereto; in the maintenance shop, where flexible cord was used as a substitute for the fixed wiring of a structure.
Recent events (2)
  • — I (O) $3315
  • — Z (S) $6630

1910.305 G01 IV B

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $0.00 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cord and cable where run through holes in walls, ceilings, or floors:    a) This violation occurred on or about February 23, 2019 and at times prior thereto; in the press department, flexible cord where run through hole in wall to power air conditioner's washer.
Recent events (2)
  • — I (O) $0
  • — Z (S) $6630

1910.305 G02 III

Other-than-serious 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $6630.00 · Current $3315.00 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:    a) The employer did not ensure flexible cords were connected to devices and fittings so that tension was not transmitted to joints or terminal screws. This violation was observed on or about January 23, 2019, in the mail room area; where the flexible cord of the UV Dry machine, model: MCS 10' conveyor,  did not have strain relief device causing a transmission of tension to joints and or terminals.
Recent events (2)
  • — I (O) $3315
  • — Z (S) $6630

View BEST PRESS, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343728549.