AURORA, IL —
OSHA Inspection: DREISILKER ELECTRIC MOTORS, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DREISILKER ELECTRIC MOTORS, INC. in 600 N. COMMERCE, AURORA, IL 60504 (NAICS 238210). OSHA activity number 344299235.
Where did this inspection happen?
- Establishment
- DREISILKER ELECTRIC MOTORS, INC.
- Site address
- 600 N. COMMERCE
- City
- AURORA
- State
- IL
- ZIP
- 60504
- Mailing
- 352 ROOSEVELT ROAD, GLEN ELLYN, IL 60137
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 1
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.332 B01
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $6000.00 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: On or about September 10, 2019 an electrical technician was performing preventative maintenance tasks, such as thermal imaging on 600 volt switch gear, that contained energized electrical components. The employee was trained in, but not familiar with safety-related work practices including the purpose and necessity of wearing electrical personal protective equipment, such as but not limited to, leather protectors, ear canal inserts and a face shield when working near energized components at or above 50 volts. The employee was exposed to the hazards of shock, electrocution and arc flash/blast injuries. Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $6000
- — Z (S) $9282
1910.333 A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: On or about September 10, 2019, an employee performed preventative maintenance such as thermal imaging, near energized electrical components. The employee did not utilize safety-related work practices to prevent injuries from direct or indirect electrical contacts, such as by wearing electrical protective equipment or shielding at all times when working on or near energized components up to 600 volts. Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $9282.00 · Current $6000.00 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: On or about September 10, 2019, an employee performing Thermal Imaging on energized General Electric Spectra Series 600 volt switch gear did not wear the electrical protective equipment appropriate for the level of exposure, exposing the employee to the hazards associated with an Arc/ Flash. including: 1) Hand protection: Leather gloves. 2) Head and face protection: Arc-rated face shield, arc-rated flash suit hood and/or balaclava. 3) Hearing protection: Hearing protectors (canal inserts). 4) Body protection: 8 cal/cm2 arc rated long sleeve shirt. Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $6000
- — Z (S) $9282
More inspections at DREISILKER ELECTRIC MOTORS, INC.
LINCOLNSHIRE, IL—1997-02-10 00:00:00
DREISILKER ELECTRIC MOTORS, INC.
View DREISILKER ELECTRIC MOTORS, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
NEW YORK, NY—2026-07-17 00:00:00
VERGARA ELECTRICAL LLC
WASHINGTON, IL—2026-07-17 00:00:00
SUNRUN INSTALLATION SERVICES, INC.
KAHULUI, HI—2026-07-16 00:00:00
RISING SUN SOLAR ELECTRIC LLC
PARKVILLE, MD—2026-07-15 00:00:00
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15 00:00:00
EDGE ELECTRICAL SYSTEMS, LLC
More inspections in IL
FRANKFORT, IL—2026-07-17 00:00:00
QUANTUM TECHNICAL SERVICES INC.
ROCK ISLAND, IL—2026-07-17 00:00:00
AUGUSTANA COLLEGE
WASHINGTON, IL—2026-07-17 00:00:00
SUNRUN INSTALLATION SERVICES, INC.
FOREST PARK, IL—2026-07-17 00:00:00
CONSERVATION OF SCULPTURE & OBJECTS STUDIO, INC.
BLUE ISLAND, IL—2026-07-17 00:00:00
PROFLOW PUMPING SOLUTIONS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344299235.