1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: ENTERPRISE ELECTRICAL CONTRACTING, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ENTERPRISE ELECTRICAL CONTRACTING, INC. in 6061 SW 80TH STREET, SOUTH MIAMI, FL 33143 (NAICS 238210). OSHA activity number 344332028.

Watch Enterprise Electrical Contracting, INC. — free Get an email when a new federal OSHA severe-injury report for Enterprise Electrical Contracting, INC. is published. One employer, no account, unsubscribe in one click.
Site address
6061 SW 80TH STREET
City
SOUTH MIAMI
State
FL
ZIP
33143
Mailing
1740 NW 69TH AVE, MIAMI, FL 33126
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
116
Ownership type
A

6 citations on file for this inspection.

1926.960 B01 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $12145.00 · Current $0.00 Reduced
29 CFR 1926.960(b)(1)(i): Employees who were not qualified were permitted to work on or with exposed energized lines or parts of equipment.  At 6061 SW 80th Street, SOUTH MIAMI, FL, 33143: On or about September 21, 2019 and at times prior, the employer exposed employees to an electrocution hazard, when a Lineman who was not trained was working from an elevated position within the MAD of exposed energized overhead power lines, and within the MAD of exposed energized parts of equipment.   NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (3)
  • — J (S) $0
  • — C (S) $12145
  • — Z (S) $12145

1926.950 B01 II

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
1926.950(b)(1)(ii): Each employee was not trained in and familiar with, any other safety practices, including applicable emergency procedures (such as pole-top and manhole rescue), that are not specifically addressed by this subpart but that are related to his or her work and are necessary for his or her safety.   At 6061 SW 80th Street, SOUTH MIAMI, FL, 33143: On or about September 21, 2019 and at times prior, a Lineman who was not trained, was exposed to an electrocution hazard when working from an elevated position within a MAD of exposed energized overhead power lines, and within the MAD of exposed energized parts of equipment.     NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.960 C01 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $12145.00 · Current $0.00 Reduced
29 CFR 1926.960(c)(1)(i): The employer did not establish minimum approach distances (MAD) no less than the distances computed by Table V-2 for ac systems:  At 6061 SW 80th Street, SOUTH MIAMI, FL, 33143: On or about September 21, 2019 and at times prior, a Lineman was exposed to an electrocution hazard when working from an elevated position, inside a bucket of an aerial lift, in close proximity to overhead energized electrical lines.    NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (3)
  • — J (S) $0
  • — C (S) $12145
  • — Z (S) $12145

1926.960 C01 III A

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.960(c)(1)(iii)(A): Employees were not insulated from energized parts through the use of rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (c)(2) of this section:  At 6061 SW 80th Street, SOUTH MIAMI, FL, 33143: On or about September 21, 2019 and at times prior, the employer exposed a Lineman who was not wearing rubber insulating gloves or rubber insulating gloves and sleeves, to an electrocution hazard, during the work process of installing an electrical cable to an electrical pole containing live overhead electrical lines.     NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.960 C01 III B

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.960(c)(1)(iii)(B): The energized part was not insulated from the employee and from any other conductive object at a different potential:  At 6061 SW 80th Street, SOUTH MIAMI, FL, 33143: On or about September 21, 2019 and at times prior, the employer exposed a Lineman to an electrocution hazard when working on energized parts of an electrical pole, such as an on and off switch that was not insulated from other conductive objects at a different potential.   NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.960 C01 III C

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.960(c)(1)(iii)(C): The employee was not insulated from any other exposed conductive object in accordance with the requirements for live-line barehand work in � 1926.964(c).  At 6061 SW 80th Street, SOUTH MIAMI, FL, 33143: On or about September 21, 2019 and at times prior, the employer exposed a Lineman to an electrocution hazard when working on energized parts of an electrical pole that were not insulated from any other exposed conductive object for live-line bare-hand work.   NOTE: CERTIFICATION AND DOCUMENTATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

View ENTERPRISE ELECTRICAL CONTRACTING, INC.'s full OSHA safety record →