1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: ALL STEEL CONSTRUCTION, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ALL STEEL CONSTRUCTION, INC. in 1002 SECTION LINE ST, MALVERN, AR 72104 (NAICS 332312). OSHA activity number 344435540.

Watch ALL Steel Construction, INC. — free Get an email when a new federal OSHA severe-injury report for ALL Steel Construction, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1002 SECTION LINE ST
City
MALVERN
State
AR
ZIP
72104
Mailing
1002 SECTION LINE ST, MALVERN, AR 72104
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
22
Ownership type
A

14 citations on file for this inspection.

1910.37 A03

Serious Gravity 5 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $8096.00 · Current $4858.00 Reduced
29 CFR 1910.37(a)(3):  Exit routes must be free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, nor may it lead into a dead-end corridor. Stairs or a ramp must be provided where the exit route is not substantially level:  At the east exit door adjacent to truck Lane, the employer did not ensure the exit route was free and unobstructed. This condition created delay in exiting the building in an emergency, and  trip and fall hazards in a fire.
Recent events (2)
  • — I (S) $4857.6
  • — Z (S) $8096

1910.37 B02

Serious Gravity 5 2 instances 22 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  At the shop, exit doors were not clearly visible and marked as "Exit" doors:  Instance a) At six exit doors, employees working in the shop were exposed to fire hazards caused by exit doors that were not clearly marked.  Instance b) At the shop on the north exterior wall, employees working in the shop were exposed to fire hazards caused by a door along an access route that was not identified by a sign that indicated its actual use e.g. exit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B06

Serious Gravity 5 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  At the south shop entrance, the exit sign is not properly affixed to the structure and is inoperable.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E02 IV D

Serious Gravity 10 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $9446.00 · Current $5668.00 Reduced
29 CFR 1910.106(e)(2)(iv)(d): Flammable liquids were not drawn from or transferred into vessels, containers, or portable tanks within a building only through a closed piping system, from safety cans, by means of a device drawing through the top, or from a container or portable tanks by gravity through an approved self-closing valve:    In the shop, employees were dispensing P-1400, a flammable liquid, into smaller containers from 55-gallon drums that were not equipped with self-closing valves, exposing employees to an explosion hazard.
Recent events (2)
  • — I (S) $5667.6
  • — Z (S) $9446

1910.106 E06 II

Serious Gravity 10 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected:  In the shop, where the employer did not ensure that 55-gallon drums of flammable liquids and gases including but not limited to Propylene, B50AZ6 primer, B50AV11 primer and P-1400 thinner were effectively bonded and grounded prior to employees dispensing to prevent discharge of sparks or static electricity.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 D01 III

Deleted Serious Gravity 5 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $6747.00 · Current $0.00 Reduced
29 CFR 1910.134(d)(1)(iii): The employer did not identify and evaluate the respiratory hazard(s) in the workplace; including a reasonable estimate of employee exposures to respiratory hazards and identification of the contaminant's chemical state and physical form:    In the paint area, the employer had not completed exposure assessments for chemicals classified as acutely toxic by inhalation and respiratory sensitizers, including but not limited to P-1400 (paint thinner), B50AZ6 (primer), and B50AV11 (primer), of employee(s) performing painting operations on structural steel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6747

1910.179 H04

Serious Gravity 10 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $9446.00 · Current $5668.00 Reduced
29 CFR 1910.179(h)(4): Hook(s) were missing latches were there was a hole to accept a latch:   In the Shop, employees operated seven Shaw-Box 5-Ton Bridge Cranes by handheld pendants, that lacked safety or throat latches on their hoisting hooks.
Recent events (2)
  • — I (S) $5667.6
  • — Z (S) $9446

1910.179 L03 III D

Serious Gravity 5 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $6747.00 · Current $4048.00 Reduced
29 CFR 1910.179(l)(3)(iii)(d): Pendant control stations were not kept clean, and/or their function labels were not kept legible:   At the shop, the employer had an 8 push button pendant control for the Shaw-box 5-ton Bridge crane that was not clearly labeled for all of the functions of the crane.
Recent events (2)
  • — I (S) $4048.2
  • — Z (S) $6747

1910.212 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $9446.00 · Current $5668.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  In the shop, the employer did not ensure unused portion of the Hyd-Mech horizontal bandsaw blade was equipped with adequate guarding.
Recent events (2)
  • — I (S) $5667.6
  • — Z (S) $9446

1910.303 G02 I

Deleted Serious Gravity 1 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $4048.00 · Current $0.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  In the shop, the employer did not ensure 240 and 440-volt electrical panel boxes and other exposed live parts were enclosed from unauthorized employees to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4048

1910.157 C01

Other-than-serious 2 instances 22 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  At the shop, fire extinguishers were not readily accessible:  Instance a:  On the west wall, the fire extinguisher was obstructed by flammable liquids.  Instance b:  On the east wall, the fire extinguisher was obstructed by heavy pieces of dunnage (lumber).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.184 E03 II

Other-than-serious 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.184(e)(3)(ii): Records of the most recent month in which each alloy steel chain sling was thoroughly inspected were not available for examination:    In the shop, the employer did not keep a record of chain sling inspections for 5-ton Shaw-box under-carriage bridge cranes.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.184 E04

Other-than-serious 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.184(e)(4): Certificate(s) of proof test were not available for new, repaired or reconditioned alloy steel chain slings:      In the shop, the employer did not ensure that each alloy steel sling for each of the eight 5-ton bridge cranes were proof tested.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  At the shop, the employer did not ensure an open working space was provided around enclosed live parts for inspection or servicing purposes.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View ALL STEEL CONSTRUCTION, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344435540.