1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: ENTERGY MISSISSIPPI, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ENTERGY MISSISSIPPI, LLC in 100 WEST CAPITOL STREET, JACKSON, MS 39269 (NAICS 221122). OSHA activity number 344450721.

Watch Entergy Mississippi, LLC — free Get an email when a new federal OSHA severe-injury report for Entergy Mississippi, LLC is published. One employer, no account, unsubscribe in one click.
Site address
100 WEST CAPITOL STREET
City
JACKSON
State
MS
ZIP
39269
Mailing
740 E. SOUTH STREET, JACKSON, MS 39201
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
4
Ownership type
A

4 citations on file for this inspection.

1910.23 C11

Serious Gravity 1 1 instance 3 exposed
Issued
Penalty
Initial $5407.00 · Current $3244.00 Reduced
29 CFR 1910.23(c)(11): Portable ladders used to gain access to an upper landing surface did not have side rails that extended at least 3 feet (0.9 m) above the upper landing surface:   (a) A.H. McCoy Federal Building Electrical Vault - On or about November 12, 2019 portable ladder used to gain access to electrical vault did not extend 3 feet above the landing surface exposing employees to fall hazards.
Recent events (2)
  • — I (S) $3244.2
  • — Z (S) $5407

1910.269 A02 I B

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $9012.00 · Current $5407.00 Reduced
29 CFR 1910.269(a)(2)(i)(B): Each employee shall also be trained in and familiar with any other safety practices, including applicable emergency procedures (such as pole-top and manhole rescue), that are not specifically addressed by this section but that are related to his or her work and are necessary for his or her safety:  (a) A.H. McCoy Federal Building Electrical Vault - On or about November 13, 2019 employees performing phase test were exposed to burn hazard.  The exposed employees were not trained to wear arc flash protective clothing when phasing.
Recent events (2)
  • — I (S) $5407.2
  • — Z (S) $9012

1910.269 L08 V

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $9012.00 · Current $5407.00 Reduced
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2:  (a) A.H. McCoy Federal Building Electrical Vault - On or about November 13, 2109 employees performing phasing a 480v circuit were exposed to an arc flash burn hazard.  Employees were not wearing arc rated protective clothing.
Recent events (2)
  • — I (S) $5407.2
  • — Z (S) $9012

1910.269 L08 V D

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(l)(8)(v)(D): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective equipment consisting of at a minimum a face shield with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2 but less than 9.0 Cal/cm2:  (a) A.H. McCoy Federal Building Electrical Vault - On or about November 13, 2109 employee assisting in the performance of a phase test was exposed to arc flash burn hazard.  Employee was not wearing an arc rated face shield.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View ENTERGY MISSISSIPPI, LLC's full OSHA safety record →

PSE&G

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344450721.