KILGORE, TX —
OSHA Inspection: NORTHEAST TEXAS POWER, LTD
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NORTHEAST TEXAS POWER, LTD in 7936 CR 294, KILGORE, TX 75662 (NAICS 423610). OSHA activity number 344865381.
Where did this inspection happen?
- Establishment
- NORTHEAST TEXAS POWER, LTD
- Site address
- 7936 CR 294
- City
- KILGORE
- State
- TX
- ZIP
- 75662
- Mailing
- PO BOX 559, CUMBY, TX 75433
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423610
- Employees
- 5
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.952 C02
- Issued
- Abate by
- Penalty
- Initial $9446.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.952(c)(2): Additional briefings. Additional job briefings were not held when significant changes, which might affect the safety of the employees, occurred during the course of the work: (a) On or about July 30, 2020 at the site employees were exposed to arc flash/blast hazards when an additional job briefing was not held though changes in procedures of the task had changed.
Recent events (2)
- — I (S) $0
- — Z (S) $9446
1926.961 C13
- Issued
- Abate by
- Penalty
- Initial $9446.00 · Current $5160.00 Reduced
General-duty citation text
29 CFR 1926.961(c)(13): Reenergizing lines and equipment. The employer did not ensure that no one initiated action to reenergize the lines or equipment at a point of disconnection until all protective grounds have been removed, all crews working on the lines or equipment release their clearances, all employees are clear of the lines and equipment, and all protective tags are removed from that point of disconnection: (a) On or about July 30, 2020 employees were exposed to arc flash/blast hazards when protective grounds were not removed prior to re-energizing the lines.
Recent events (2)
- — I (S) $5160
- — Z (S) $9446
More inspections at NORTHEAST TEXAS POWER, LTD
MINEOLA, TX—2020-11-10 00:00:00
NORTHEAST TEXAS POWER, LTD
View NORTHEAST TEXAS POWER, LTD's full OSHA safety record →
More inspections in this industry (NAICS 423610)
FAIRFIELD, CA—2026-07-10
MAIN ELECTRIC SUPPLY
SANTA ANA, CA—2026-07-06
SAF-T-CO SUPPLY INC.
COLUMBUS, IN—2026-07-02
OPTIMAS OE SOLUTIONS
EUGENE, OR—2026-06-03
317744393 - CENTURY LIGHTING INC
MILPITAS, CA—2026-06-02
CONTRACTORS ELECTRICAL DISTRIBUTORS
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344865381.