Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: GURTZ ELECTRIC CO.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GURTZ ELECTRIC CO. in 14 W. SUPERIOR ST., CHICAGO, IL 60654 (NAICS 238210). OSHA activity number 345347066.

Watch Gurtz Electric CO. — free Get an email when a new federal OSHA severe-injury report for Gurtz Electric CO. is published. One employer, no account, unsubscribe in one click.
Establishment
GURTZ ELECTRIC CO.
Site address
14 W. SUPERIOR ST.
City
CHICAGO
State
IL
ZIP
60654
Mailing
77 W. SEEGERS RD., ARLINGTON HEIGHTS, IL 60005
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
23
Ownership type
A

3 citations on file for this inspection.

1926.20 B02

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $13653.00 · Current $0.00 Reduced
29 CFR  1926.20(b)(2):  The employer did not initiate and maintain programs which provided for frequent and regular inspections of the job site, materials and equipment to be made by a competent person(s).  a.  On or about June 7, 2021, at the above addressed jobsite, the employer did not ensure that an inspection of the Fluke 1587 FC Insulation Multimeter S/N 40090026 was conducted by a competent person.
Recent events (2)
  • — I (O) $0
  • — Z (S) $13653

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Penalty
Initial $13653.00 · Current $13653.00
29 CFR  1926.416(a)(1):  Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  a.  On or about June 7, 2021, at the above addressed jobsite, employees performing bus duct installation operations on the 55th floor were not protected against electric shock by de-energizing and grounding the circuit or by guarding it effectively by insulation or other means, thereby exposing the employees to electrical hazards.
Recent events (2)
  • — I (S) $13653
  • — Z (S) $13653

1926.417 B

Serious Gravity 10 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1926.417(b): Equipment or circuits that were de-energized did not have tags attached at all points where such equipment or circuits could be energized:  a.  On or about June 4, 2021, at the above addressed jobsite,  an employee visually verified that the "Bus Duct A4" SIEMENS 1600 Amp breaker was de-energized, but did not render it inoperative and tag it to prevent re-energization, thereby exposing employees to electrical hazards, including, but not limited to, arc flash hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View GURTZ ELECTRIC CO.'s full OSHA safety record →