1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: ENTACT, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ENTACT, LLC in 1 ILLINOIS ST., LAWRENCEVILLE, IL 62439 (NAICS 562910). OSHA activity number 345658793.

Watch Entact, LLC — free Get an email when a new federal OSHA severe-injury report for Entact, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ENTACT, LLC
Site address
1 ILLINOIS ST.
City
LAWRENCEVILLE
State
IL
ZIP
62439
Mailing
1 OAK DRIVE, WESTMONT, IL 60559
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562910
Employees
6
Ownership type
A

3 citations on file for this inspection.

1910.269 L01 I

Other-than-serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $8806.00 · Current $5870.00 Reduced
29 CFR  1910.269(l)(1)(i):  Unqualified employees performed work on or with exposed energized lines or parts of equipment:  On or about November 17, 2021, an employee, who was not qualified to perform work on exposed energized lines, placed orange plastic fencing over utility lines.
Recent events (3)
  • — F (O) $5870
  • — C (S) $8806
  • — Z (S) $8806

1910.269 L03 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $8806.00 · Current $0.00 Reduced
29 CFR  1910.269(l)(3)(i):The employer did not establish minimum approach distances no less than the distances computed by Table R-3 for ac systems or Table R-8 for dc systems:  On or about November 17, 201, the employer did not establish minimum approach distances for utility line work, and permitted an employee to work within an approximate one foot distance of an energized line.
Recent events (3)
  • — F (S) $0
  • — C (S) $8806
  • — Z (S) $8806

1910.269 N02

Other-than-serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $8806.00 · Current $8806.00
29 CFR  1910.269(n)(2):  For any employee to work transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section:  On or about November 17, 2021, an employee was permitted to work on electrical lines, which the employer considered de-energized; however, the employer did not ensure the lines were de-energized in accordance with 29 CFR 1910.269 paragraph (m), and did not ensure the lines were grounded as specified in 29 CFR 1910.269 paragraphs (n)(3) through (n)(8).
Recent events (3)
  • — F (O) $8806
  • — C (S) $8806
  • — Z (S) $8806

ENTACT LLC

ENTACT LLC

ENTACT LLC

ENTACT LLC

View ENTACT, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345658793.