On , OSHA opened a complaint safety inspection of EOS HOSPITALITY LLC in 1001 14TH. ST, NW, WASHINGTON, DC 20005 (NAICS 721110). OSHA activity number 345884415.

Watch EOS Hospitality LLC — free Get an email when a new federal OSHA severe-injury report for EOS Hospitality LLC is published. One employer, no account, unsubscribe in one click.
Establishment
EOS HOSPITALITY LLC
Site address
1001 14TH. ST, NW
City
WASHINGTON
State
DC
ZIP
20005
Mailing
65 EAST 55TH ST. 33RD FLOOR, NEW YORK, NY 10022
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
35
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6340.00 · Current $4755.00 Reduced
29 CFR  1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    (a) Kitchen, Pasta Processing Room - On or about, April 6, 2022, kitchen workers were exposed to an electrical shock hazard from the 120 volt surge protector power strip used to provide power to a wine cooler (refrigerator) in an industrial kitchen.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $4755
  • — Z (S) $6340

1910.304 B04 II B

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4:  (a) Kitchen, Pasta Processing Room - On or about April 6, 2022, cord sets plugged into the 12 amp outlets in a surge protector power strip overloaded the capacity of the power strip outlets, in that, one of the cord sets powered a 120 volt Cavavin commercial wine chiller which operates at 15 Amps. according to the manufacturer's equipment manual.  29 CFR 1903.19(c), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  (a) Kitchen, Pasta Processing Room - On or about April 6, 2022, a cord set was used in lieu of permanent wiring to provide electrical power to a 120 volt Cavavin commercial wine chiller.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0