TULSA, OK —
OSHA Inspection: LIBRA ELECTRIC COMPANY
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of LIBRA ELECTRIC COMPANY in 8605 S. ELWOOD AVE ON TAXIWAY L (LIMA) BETWEEN RUNWAY 19R/01L AND 19L/01R, TULSA, OK 74132 (NAICS 238210). OSHA activity number 346709769.
Where did this inspection happen?
- Establishment
- LIBRA ELECTRIC COMPANY
- Site address
- 8605 S. ELWOOD AVE ON TAXIWAY L (LIMA) BETWEEN RUNWAY 19R/01L AND 19L/01R
- City
- TULSA
- State
- OK
- ZIP
- 74132
- Mailing
- 4736 ENTERPRISE DR., OKLAHOMA CITY, OK 73128
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 50
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.416 A01
- Issued
- Abate by
- Penalty
- Initial $10938.00 · Current $6563.00 Reduced
General-duty citation text
29 CFR 1926.416 (a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work: On or about May 15, 2023, and at times prior to, Taxiway L (Lima), employees performing electrical isolating procedures were not protected from live electrical circuits in the course of their work, exposing employees to electrical hazards.
Recent events (2)
- — I (O) $6562.8
- — Z (S) $10938
1926.416 A03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.416 (a)(3): The employer began work without determining if employees could contact any part of an energized circuit and did not post warning signs and advise employees of the location of the circuit, hazards, and protective measures they need to take. On or about May 15, 2023, and at times prior to, employees were not trained on protective measures to be used when working with energized electrical circuits for the following taxiway lights: a. Taxiway A (alpha), and b. Taxiway L (lima).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.417 A
- Issued
- Abate by
- Penalty
- Initial $10938.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged. On or about May 15, 2023, and at times prior to, controls within the series circuit for taxiway lights that needed to be de-energized were not tagged, exposing employees to electrical hazards for the following instances: a. Taxiway A (alpha), and b. Taxiway L (lima).
Recent events (2)
- — I (S) $0
- — Z (S) $10938
1926.417 B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $6563.00
General-duty citation text
29 CFR 1926.417(b): Equipment or circuits that were de-energized were not rendered inoperative and did not have tags attached at all points where such equipment or circuits could be energized: On or about May 15, 2023, and at times prior to, Taxiway L (Lima), a series circuit was in operation and did not have tags when employees worked on the circuit, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $6562.8
- — Z (S) $0
1926.95 A
- Issued
- Abate by
- Penalty
- Initial $10938.00 · Current $6563.00 Reduced
General-duty citation text
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided. On or about May 15, 2023, and at times prior to, Taxiway L (Lima), employees working on or near energized electrical equipment for taxiway lights, did not have a barrier or personal protective equipment and were exposed to electrical hazards.
Recent events (2)
- — I (O) $6562.8
- — Z (S) $10938
More inspections at LIBRA ELECTRIC COMPANY
OKLAHOMA CITY, OK—2017-08-15 00:00:00
LIBRA ELECTRIC COMPANY
View LIBRA ELECTRIC COMPANY's full OSHA safety record →
More inspections in this industry (NAICS 238210)
NEW YORK, NY—2026-07-17 00:00:00
VERGARA ELECTRICAL LLC
WASHINGTON, IL—2026-07-17 00:00:00
SUNRUN INSTALLATION SERVICES, INC.
KAHULUI, HI—2026-07-16 00:00:00
RISING SUN SOLAR ELECTRIC LLC
PARKVILLE, MD—2026-07-15 00:00:00
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15 00:00:00
EDGE ELECTRICAL SYSTEMS, LLC
More inspections in OK
TULSA, OK—2026-07-15 00:00:00
LA UNION 7 LLC
STILLWATER, OK—2026-07-13 00:00:00
LATSHAW DRILLING COMPANY
BROKEN ARROW, OK—2026-07-10 00:00:00
AMERICAN WHEATLEY
TINKER AFB, OK—2026-07-09 00:00:00
U.S. DEPARTMENT OF DEFENSE, TINKER AIR FORCE BASE
OCHELATA, OK—2026-07-08 00:00:00
WALMART, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346709769.