OSHA Inspection: LND TECHNICAL SERVICES, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of LND TECHNICAL SERVICES, LLC in 55501 DOT ROAD, PUEBLO, CO 81001 (NAICS 238210). OSHA activity number 346842164.

Watch LND Technical Services, LLC — free Get an email when a new federal OSHA severe-injury report for LND Technical Services, LLC is published. One employer, no account, unsubscribe in one click.
Site address
55501 DOT ROAD
City
PUEBLO
State
CO
ZIP
81001
Mailing
9337 KAY FREEWAY ST. STE B-5104, HOUSTON, TX 77028
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
22
Ownership type
A

12 citations on file for this inspection.

1910.132 A

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6250.00 · Current $4750.00 Reduced
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered:  a) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, exposed employees to electrical hazards in that the employer did not provide or require employee use of insulating, voltage-rated gloves during the applications of testing grounds to transformer winding terminals and during the discharge of transformer windings after high-voltage testing in Substation 2.
Recent events (2)
  • — I (S) $4750
  • — Z (S) $6250

1910.132 D01

Other-than-serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment:   a) On or about July 13, 2023, and times prior, LND Technical Services, LLC, did not perform a hazard assessment of work activities at Substation 2 to determine what hazards were present or could be present during the course of work, which would necessitate the use of personal protective equipment.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.269 A02 I A

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6250.00 · Current $0.00 Reduced
29 CFR 1910.269(a)(2)(i)(A): Each employee was not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments:  a) On or about July 13, 2023, and times prior, LND Technical Services, LLC, exposed employees to electrical hazards in that they did not provide electrical safety training in safe work practices and procedures to employees before, or at any point during testing and maintenance work at Substation 2.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6250

1910.269 A03 III

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6250.00 · Current $6250.00
29 CFR 1910.269(a)(3)(iii): The contract employer and the host employer did not coordinate their work rules and procedures so that each employee of the contract employer and the host employer was protected as required by this section:  a) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, as a contract employer, did not coordinate or communicate by any means, site-specific, electrical safety work rules and procedures regarding high-voltage testing and maintenance activities in Substation 2, with the host employer, ENSCO, Inc.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $6250
  • — Z (S) $6250

1910.269 C01 I

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6250.00 · Current $0.00 Reduced
29 CFR 1910.269(c)(1)(i): In assigning an employee or a group of employees to perform a job, the employer did not provide the employee in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by paragraph (a)(4) of this section:  a) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, did not possess nor provide to the employee in charge of the job, at any point before or during work at Substation 2, the following information, verbal or written:  (1) Information specific to Substation 2 regarding the presence and need of protective grounds and equipment grounding conductors; (2) Information specific to Substation 2 regarding the condition of protective grounds and equipment grounding conductors; (3) Information specific to Substation 2 regarding the location and presence of circuits and equipment as well as the location and presence of electric supply lines; (4) Information regarding the design and operation of Substation 2.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6250

1910.269 C01 II

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $4500.00
29 CFR 1910.269(c)(1)(ii): The employer did not ensure that the employee in charge conducts a job briefing that meets paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before they start each job:  a) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, did not provide, at any point before or during work, a Substation 2-specific, pre-job briefing for employees that addressed the following items related to the scope of work:  (1) hazards associated with the job; (2) work procedures involved; (3) special precautions; (4) energy-source controls; and (5) requirement for personal protective equipment.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $4500
  • — Z (S) $0

1910.269 M03 II

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6250.00 · Current $6250.00
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy might be supplied to the particular lines and equipment were de-energized / inoperable (i.e. open) and then did not ensure that such means were tagged to indicate that employees were at work:  a) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, did not ensure the Alternating Current Switchgear main circuit breaker was in the open position, thereby eliminating potential power transfer backfeeds.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $6250
  • — Z (S) $6250

1910.269 M03 VII

Deleted Serious Gravity 10 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(m)(3)(vii): The employer did not ensure the installation of protective grounds as required by paragraph (n) of this section:  a) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, did not require the use of temporary personal protective grounds on the Medium Voltage (MV) side of Transformer T201 during reconnection of cables to terminal windings after high voltage-inducing tests were completed on the MV side.   This exposed employees to electrical hazards.  b) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, did not require the use of high voltage (HV) side, built-in grounding disconnect switches on Transformer T201 during High Voltage (HV) side reconnections of bushings to conductors after high voltage-inducing tests were completed on the HV side of Transformer T201.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 O02 I

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $6250.00 · Current $6250.00
29 CFR 1910.269(o)(2)(i): The employer did not establish and enforce work practices for the protection of each worker from the hazards of high-voltage or high-power testing at all test areas, temporary and permanent:  a) On or about July 13, 2023, LND Technical Services, LLC, did not establish and enforce site-specific work practices and procedures addressing existing hazards, or hazards that have the potential to exist, to employees before or at any point during high voltage-inducing testing and maintenance work at Substation 2.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $6250
  • — Z (S) $6250

1910.269 O02 II

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(o)(2)(ii): The employer shall ensure that each employee, upon initial assignment to the test area, receives training in safe work practices, with retraining provided as required by paragraph (a)(2) of this section:   a) On or about July 13, 2023, LND Technical Services, LLC, did not provide training in safe work practices and procedures addressing electrical hazards associated with high voltage-inducing testing to employees before, or at any point during work at Substation 2.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 A02 VII

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(a)(2)(vii): The employer did not ensure that each employee had demonstrated proficiency in the work practices involved before that employee was considered as having completed training:    a)  On or about July 13, 2023, and at times prior, LND Technical Services, LLC, did not require each employee to demonstrate proficiency in safe work practices and procedures regarding high voltage-inducing testing and maintenance work in Substation 2 before, or at any point, during work operations.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Other-than-serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $2678.00 · Current $0.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) On or about July 13, 2023, and at times prior, LND Technical Services, LLC, did not ensure flexible cord sets were used and installed properly (i.e.  not daisy-chained).  This exposed employees to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (S) $2678

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346842164.