KISSIMMEE, FL —
OSHA Inspection: L & R UNDERGROUND SOLUTIONS, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of L & R UNDERGROUND SOLUTIONS, INC. in BIG SKY AND GAVIN SKY DR., KISSIMMEE, FL 34744 (NAICS 237130). OSHA activity number 346859531.
Where did this inspection happen?
- Establishment
- L & R UNDERGROUND SOLUTIONS, INC.
- Site address
- BIG SKY AND GAVIN SKY DR.
- City
- KISSIMMEE
- State
- FL
- ZIP
- 34744
- Mailing
- 2167 KEYSTONE AVE., SAINT CLOUD, FL 34772
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 5
- Ownership type
- A
Citations
6 citations on file for this inspection.
1926.21 B02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.21(b)(2):The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury: a) On or about 7/25/2023, at the job site, employees working near electrical equipment were not trained to be able to recognize electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.950 B01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.950(b)(1)(i): Each employee was not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this subpart that pertain to his or her job assignments. a) On or about 07/25/2023, at the job site, employees working near electrical equipment had not received any instruction/training on electrical safety work practices.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.960 B01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.960(b)(1)(i): Unqualified employees worked on and/or with exposed energized lines and/or parts of equipment. a) On or about 07/25/2023, at the job site, employees working on or near the electrical switch box were not qualified, exposing themselves to a 14,000 volts electrical hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.960 B02
- Issued
- Abate by
- Penalty
- Initial $4839.00 · Current $4355.00 Reduced
General-duty citation text
29 CFR 1926.960(b)(2): Electric lines and equipment were not considered or treated as energized when they had not been de-energized in accordance with 1926.961. a) On or about 07/25/2023, at the job site, the employees working on or near the electrical switch box did not de-energize the live parts, exposing employees to a 14,000 volts electrical hazard.
Recent events (2)
- — I (S) $4355.1
- — Z (S) $4839
1926.960 C01 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.960(c)(1)(iii): The employer did not ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless the measures outlined in 1926.960(c)(1)(iii)(A) - (C) were met: a) On or about 07/25/2023, at the job site, employees working on or near the electrical switch box did not de-energize the live parts, and were within the minimum approach distance, exposing themselves to a 14,000 volts electrical hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.952 A01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.952(a)(1): In assigning an employee or a group of employees to perform a job, the employer did not provide the employee in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by � 1926.950(d). a) On or about 07/25/2023, at the job site, employees working on or near the electrical switch box did not conduct a job briefing prior to work.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 237130)
TWINSBURG, OH—2026-07-14 00:00:00
ERVIN CABLE CONSTRUCTION, LLC
LEXINGTON, KY—2026-07-09 00:00:00
69310 - DAVIS H ELLIOT COMPANY INC
POUGHQUAG, NY—2026-07-09 00:00:00
MK SHARP LLC.
FEDERAL WAY, WA—2026-07-08 00:00:00
WA317992027 - OPEN COUNTRY LLC
KENMORE, WA—2026-07-08 00:00:00
WA317991980 - CASCADE TOWER & RIGGING INC
More inspections in FL
DELAND, FL—2026-07-16 00:00:00
BALL FABRICS
GAINESVILLE, FL—2026-07-16 00:00:00
WACKY SAUCES LLC
FORT WALTON BEACH, FL—2026-07-16 00:00:00
WASTE MANAGEMENT, INC. OF FLORIDA
PONCE INLET, FL—2026-07-16 00:00:00
RESOLUTE ROOFING LLC
PALM COAST, FL—2026-07-16 00:00:00
J & J TREE EXPERTS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346859531.