1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: POWER ELECTRONICS USA, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of POWER ELECTRONICS USA, INC. in 8690 HOGAN RD, LIVE OAK, FL 32060 (NAICS 221114). OSHA activity number 347055931.

Watch Power Electronics USA, INC. — free Get an email when a new federal OSHA severe-injury report for Power Electronics USA, INC. is published. One employer, no account, unsubscribe in one click.
Site address
8690 HOGAN RD
City
LIVE OAK
State
FL
ZIP
32060
Mailing
1510 N HOBSON ST., GILBERT, AZ 85233
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221114
Employees
1
Ownership type
A

4 citations on file for this inspection.

1910.269 B01 II

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $16131.00 · Current $12098.00 Reduced
29 CFR 1910.269(b)(1)(ii): For fixed work locations the number of trained persons available was not sufficient to ensure that each employee exposed to electric shock could be reached within four (4) minutes by a trained person:    a. At Florida Power and Light's Sunshine Solar power Farm, located at 8690 Hogan Road in Live Oak Florida: On or about October 23, 2023, the employer exposed employees to electrical shock and burn hazards, in that at least one additional person who was trained in First Aid was not available at the worksite to render first-aid with four (4) minutes.
Recent events (2)
  • — I (S) $12098.25
  • — Z (S) $16131

1910.269 L02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.269(l)(2)(i): Except as provided in paragraph (l)(2)(ii) of this section, at least two employees shall be present while any employees perform the following types of work; (E) Other work that exposes an employee to electrical hazards greater than, or equal to, the electrical hazards posed by operations listed specifically in paragraphs (l)(2)(i)(A) through (l)(2)(i)(D) of this section:    a. At Florida Power and Light's Sunshine Solar Power Farm, located at 8690 Hogan Road in Live Oak Florida: On or about October 23, 2023, the employer exposed employees to electrical shock and burn hazards, in that two employees were not present while performing the removal and installation of module at the number 10 Inverter, while exposed to 645 VAC.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 D02 IV D

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $16131.00 · Current $12098.00 Reduced
29 CFR 1910.269(d)(2)(iv)(D): The procedure did not clearly and specifically outline specific requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures.  a. At Florida Power and Light's Sunshine Solar power Farm, located at 8690 Hogan Road in Live Oak Florida: The employer exposed employees to electrical shock and burn hazards, in that the established procedures for remotely shutting down and testing an inverter was not clear or specific.
Recent events (2)
  • — I (S) $12098.25
  • — Z (S) $16131

1910.269 D06 II

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $16131.00 · Current $12098.00 Reduced
29 CFR 1910.269(d)(6)(ii): The machine or equipment was not turned off or shut down using the procedures established for the machine or equipment. An orderly shutdown was not used to avoid any additional or increased hazards to employees as a result of the equipment stoppage:    a. At Florida Power and Light's Sunshine Solar Power Farm, located at 8690 Hogan Road in Live Oak Florida: On or about October 23, 2023, the employer exposed employees to electrical shock and burn hazards, in that the #10 inverter was not shut down using the employer's established procedures.
Recent events (2)
  • — I (S) $12098.25
  • — Z (S) $16131

View POWER ELECTRONICS USA, INC.'s full OSHA safety record →