TERRELL, TX —
OSHA Inspection: LONGHORN FABRICATION INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of LONGHORN FABRICATION INC. in 3200 AIRPORT DRIVE, TERRELL, TX 75160 (NAICS 332812). OSHA activity number 347118549.
Where did this inspection happen?
- Establishment
- LONGHORN FABRICATION INC.
- Site address
- 3200 AIRPORT DRIVE
- City
- TERRELL
- State
- TX
- ZIP
- 75160
- Mailing
- 3200 AIRPORT DRIVE, TERRELL, TX 75160
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332812
- Employees
- 105
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.147 C04 II C
- Issued
- Abate by
- Penalty
- Initial $14518.00 · Current $14518.00
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(C): The energy control procedure did not clearly and specifically outline the steps for placement, removal and transfer of lockout devices or tagout devices and the responsibility for them: (a) On or about November 21, 2023, the employer did not ensure the energy control of the lockout/tagout specific procedures were develop and followed for the Steelman bake powder coat oven. Employees were exposed to an amputation hazard.
Recent events (2)
- — I (S) $14518
- — Z (S) $14518
1910.147 C06 II
- Issued
- Abate by
- Penalty
- Initial $14518.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(ii): The employer did not certify that the periodic inspections have been performed. The certification did not identify the machine or equipment on which the energy control procedure was being utilized, the date of the inspection, the employees included in the inspection, and the person performing the inspection: (a) On or about November 21, 2023, the employer did not ensure the energy control periodic inspections were performed and certified of the Lockout/tagout procedures.
Recent events (2)
- — I (S) $0
- — Z (S) $14518
1910.147 D04 I
- Issued
- Abate by
- Penalty
- Initial $14518.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.147(d)(4)(i): Lockout or tag out devices were not affixed to each energy isolating device by authorized employees: (a) On or about November 21, 2023, where employees working in the Paint department, on the small oven, Steelman bake powder coat oven, model: 10914 GSP, serial: 92163 and were exposed to amputation hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $14518
1910.303 B07 I
- Issued
- Abate by
- Penalty
- Initial $14518.00 · Current $14518.00
General-duty citation text
29 CFR 1910.303(b)(7)(i):Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment: On or about November 21, 2023, the employer did not fill-in the unused openings on the Steelman small bake powder coat oven and Steelman large bake powder coat oven (a) Paint shop, Steelman small bake oven, model no. 10914GSP, serial no. 92163 (b) Paint shop. Steelman large oven. Employer identifies as ID#8-5'X10'X26'.
Recent events (2)
- — I (S) $14518
- — Z (S) $14518
1910.147 C07 I
- Issued
- Abate by
- Penalty
- Initial $1165.00 · Current $1165.00
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees: (a) On or about November 21, 2023, where the employer did not ensure the energy control periodic inspections were performed and certified of the Lockout/tagout procedures.
Recent events (2)
- — I (O) $1165
- — Z (O) $1165
More inspections in this industry (NAICS 332812)
WICHITA, KS—2026-07-10
DIVERSIFIED SERVICES, INC.
SHARON, PA—2026-07-09
NLMK SHARON COATING, LLC
CUDDY, PA—2026-07-08
SUPERIOR POWDER COATING INC
GRAND HAVEN, MI—2026-07-07
LAKESHORE CUSTOM POWDER COATING INC
AMBRIDGE, PA—2026-06-24
CENTRIA
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source