MEMPHIS, TN —
OSHA Inspection: BUZZI UNICEM, USA
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUZZI UNICEM, USA in 2415 PIER STREET, MEMPHIS, TN 38113 (NAICS 327320). OSHA activity number 347458788.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUZZI UNICEM, USA
- Site address
- 2415 PIER STREET
- City
- MEMPHIS
- State
- TN
- ZIP
- 38113
- Mailing
- P.O. BOX 13204, MEMPHIS, TN 38113
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327320
- Employees
- 11
- Ownership type
- A
Citations
4 citations on file for this inspection.
1917.112 C03
- Issued
- Jul 10, 2024
- Penalty
- Initial $12,098 · Current $7,259 Reduced
General-duty citation text
29 CFR 1917.112(c)(3): The top surface of guardrails installed after October 3, 1983, was not 42 inches, plus or minus 2 inches high: (a) Buzzi Memphis Terminal, gangway platform: On or about 5/02/2024, and at times prior, the employer exposed employees to falls greater than four feet, in that a work platform on the gangway raised the floor level so that the top rail was at a height of 26 inches.
Recent events (2)
- — I (S) $7258.8
- — Z (S) $12098
1910.303 F01
- Issued
- Jul 10, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) Buzzi working barge, North side, beneath and West of gangway: On or about 5/03/2024, and at times prior, the employer exposed employees to possible shock hazards, in that the breakers inside of a 480-volt panel box were not labeled to indicate their purpose.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01
- Issued
- Jul 10, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: (a) Buzzi working barge, workshop, South wall: On or about 5/03/2024, and at times prior, the employer exposed employees to electrical shock hazards, in that the area in front of three electrical panel boxes was being used for storage blocking access to the electrical panels.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B03 III
- Issued
- Jul 10, 2024
- Penalty
- Initial $971 · Current $583 Reduced
General-duty citation text
29 CFR 1910.305(b)(3)(iii): Covers for boxes were not permanently marked "HIGH VOLTAGE". (a) Buzzi working barge, North side, beneath and West of gangway: On or about 5/03/2024, and at times prior, the employer exposed employees to possible shock hazards, in that the outside of a 480-volt panel box was not labeled with warning signs. (b) Buzzi working barge, workshop, South wall, left panel box: On or about 5/03/2024, and at times prior, the employer exposed employees to possible shock hazards, in that the outside of a 480-volt panel box was not labeled with warning signs. (c) Buzzi working barge, workshop, South wall, center panel box: On or about 5/03/2024, and at times prior, the employer exposed employees to possible shock hazards, in that the outside of a 480-volt panel box was not labeled with warning signs. (d) Buzzi working barge, workshop, South wall, right panel box: On or about 5/03/2024, and at times prior, the employer exposed employees to possible shock hazards, in that the outside of a 480-volt panel box was not labeled with warning signs.
Recent events (2)
- — I (O) $582.6
- — Z (O) $971
More inspections at Buzzi Unicem, USA
View Buzzi Unicem, USA's full OSHA safety record →
More inspections in this industry (NAICS 327320)
More inspections in TN
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347458788.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.