EAU CLAIRE, WI —
OSHA Inspection: DRYLOCK TECHNOLOGIES, LTD.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of DRYLOCK TECHNOLOGIES, LTD. in 3921 NORTH HASTINGS WAY, EAU CLAIRE, WI 54703 (NAICS 322291). OSHA activity number 347463952.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DRYLOCK TECHNOLOGIES, LTD.
- Site address
- 3921 NORTH HASTINGS WAY
- City
- EAU CLAIRE
- State
- WI
- ZIP
- 54703
- Mailing
- 3921 NORTH HASTINGS WAY, EAU CLAIRE, WI 54703
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322291
- Employees
- 298
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.137 C02 VIII
- Issued
- Sep 6, 2024
- Abate by
- Sep 20, 2024
- Penalty
- Initial $11,754 · Current $8,228 Reduced
General-duty citation text
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and/or the maximum intervals between tests were not conducted in accordance with Table I-4 and Table I-5: (a) Production area; On or about May 6, 2024, and dates prior, the employer did not ensure the class 0 electrical gloves issued to authorized employees were tested to the voltage listed in Table I-4 and did not follow the testing intervals listed in Table I-5.
Recent events (2)
- — I (S) $8227.8
- — Z (S) $11754
1910.333 A01
- Issued
- Sep 6, 2024
- Abate by
- Sep 20, 2024
- Penalty
- Initial $9,795 · Current $6,857 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: (a) Throughout the production area; On or about May 6, 2024, and dates prior, the employees working on 24V DC energized electrical equipment were exposed to the hazards of adjacent equipment and conductors, energized from 120V AC up to 480V AC, inside the same electrical cabinets.
Recent events (2)
- — I (S) $6856.5
- — Z (S) $9795
1910.147 C06 I
- Issued
- Sep 6, 2024
- Abate by
- Sep 20, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: (a) EAP2; On or about May 6, 2024, and dates prior, the employer did not conduct a periodic inspection of the energy control procedures for the EAP2 adult incontinence production line at least annually to ensure the procedures were effective and conformed to the OSHA standards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Drylock Technologies, LTD.
View Drylock Technologies, LTD.'s full OSHA safety record →
More inspections in this industry (NAICS 322291)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347463952.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.