1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: CLEVELAND-CLIFFS CLEVELAND WORKS, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CLEVELAND-CLIFFS CLEVELAND WORKS, LLC in STIP MILL WATER TREATMENT FACILITY 1555 HARVARD AVE, CLEVELAND, OH 44105 (NAICS 331110). OSHA activity number 347579781.

Watch Cleveland-Cliffs Cleveland Works, LLC — free Get an email when a new federal OSHA severe-injury report for Cleveland-Cliffs Cleveland Works, LLC is published. One employer, no account, unsubscribe in one click.
Site address
STIP MILL WATER TREATMENT FACILITY 1555 HARVARD AVE
City
CLEVELAND
State
OH
ZIP
44105
Mailing
ATTN: TRENT MEYERS 3060 EGGERS AVENUE, CLEVELAND, OH 44105
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331110
Employees
2069
Ownership type
A

6 citations on file for this inspection.

1910.303 B07 I

Serious Gravity 5 1 instance 4 exposed
Issued
Penalty
Initial $8619.00 · Current $8619.00
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.  a) On or about June 26, 2024, the employer did not ensure unused openings in the Cutler-Hammer UNITROL Motor Control Center (Serial Number - 6AFI386853-A), located in the CRANE MCC room, were effectively closed exposing employees to a 440-volt electrical shock hazard when locking out skimmer buckets, pulling fuses, switching disconnects and maintaining the crane and pit skimmers.
Recent events (2)
  • — I (S) $8619
  • — Z (S) $8619

1910.303 E01 I

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $8619.00 · Current $0.00 Reduced
29 CFR 1910.303(e)(1): Identification of manufacturer and ratings. Electric equipment may not be used unless the following markings have been placed on the equipment:   29 CFR 1910.303(e)(1)(i): The manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified;  a) On or about June 26, 2024, the employer did not ensure the manufacture's name, trademark, or other descriptive markings were on the electrical disconnects for the LIGHTNIN mixers and lights located in the lime room and hanging on the light pole outside the electrical room, exposing maintenance electricians to electrical shocks hazards during preventative maintenance and repairs.
Recent events (2)
  • — I (O) $0
  • — Z (S) $8619

1910.303 E01 II

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(e)(1): Identification of manufacturer and ratings. Electric equipment may not be used unless the following markings have been placed on the equipment:  29 CFR 1910.303(e)(1)(ii): Other markings giving voltage, current, wattage, or other ratings as necessary.  a) On or about June 26, 2024, the employer did not ensure the voltage, current, wattage, or other markings were on the electrical disconnects for the LIGHTNIN mixers and lights located in the lime room and hanging on the light pole outside the electrical room exposing maintenance electricians to electrical shocks hazards during preventative maintenance and repairs.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 G01 I A

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $8619.00 · Current $8619.00
29 CFR 1910.303(g)(1)(i)(A): The depth of the working space in the direction of access to live parts may not be less than indicated in Table S-1. Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed;  a) On or about June 26, 2024, the employer did not ensure Maintenance Electricians (MTE) conducting preventative maintenance on live parts of the square D safety switch in the Millwright Room had a minimum depth of three-foot (3') working space (Table S-1, 151-600-volts and condition A) exposing them to an electrical shock hazard.
Recent events (2)
  • — I (S) $8619
  • — Z (S) $8619

1910.303 G02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $8619.00 · Current $8619.00
29 CFR  1910.303(g)(2)(i): Except as�elsewhere required�or permitted�by this�standard, live�parts of�electric equipment�operating at�50 volts�or more�shall be�guarded against�accidental contact by�use of�approved cabinets�or other�forms of�approved enclosures�or by any of the means listed in 1910.303(g)(2)(i)(A) - (D).  a) On or about June 26, 2024, the employer did not ensure employees controlling and/or maintaining the Sludge Pump (Moyno pump) using the P302A Sludge Pump control in the MCC6 room were guarded against accidental contact of the 480-volt electrical conductors by use of an approved cabinet exposing them to electrical shock hazards.
Recent events (2)
  • — I (S) $8619
  • — Z (S) $8619

1910.303 G02 II

Other-than-serious Gravity 1 1 instance 5 exposed
Issued
Penalty
Initial $6464.00 · Current $0.00 Reduced
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment is likely to be exposed to physical damage, enclosures or guards shall be so arranged and of such strength as to prevent such damage.  On or about June 26, 20241, the employer did not ensure the electrical disconnects on the light pole outside the electrical shop were guarded to prevent damage from tractor trailers, PIVs, caustic trucks, personal vehicles, and aerial lifts exposing the drivers of these vehicles to electrical shock hazards.
Recent events (2)
  • — I (O) $0
  • — Z (S) $6464