OSWEGO, NY —
OSHA Inspection: NOVELIS CORPORATION
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NOVELIS CORPORATION in 448 COUNTY ROUTE 1A, OSWEGO, NY 13126 (NAICS 331318). OSHA activity number 347801995.
Where did this inspection happen?
- Establishment
- NOVELIS CORPORATION
- Site address
- 448 COUNTY ROUTE 1A
- City
- OSWEGO
- State
- NY
- ZIP
- 13126
- Mailing
- 448 COUNTY ROUTE 1A, OSWEGO, NY 13126
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331318
- Employees
- 1165
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.333 A01
- Issued
- Abate by
- Penalty
- Initial $16550.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.333(a)(1):The employer failed to ensure that live parts were deenergized before employees began to work on or near live parts. a) Novelis Inc., 448 County Route 1A, Oswego, New York 13126, Stores Pole Barn. On or about 10/1/2024, the employer failed to ensure that a live part in a 460 Volt AC electrical panel was deenergized before an employee began work on or near the live part resulting in that employee receiving an electrical shock.
Recent events (2)
- — I (S) $0
- — Z (S) $16550
1910.333 B02 IV B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B):Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that circuit elements and equipment parts were deenergized: a) Novelis Inc., 448 County Route 1A, Oswego, New York 13126, Stores Pole Barn. On or about 10/1/2024, a qualified person did not use test equipment to test and verify a 460 Volt AC electrical panel, was de-energized prior to performing work. When an employee began working on or near a live part on the 460 Volt AC electrical panel, the employee received an electrical shock from a live part.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: a) Novelis Inc., 448 County Route 1A, Oswego, New York 13126, Stores Pole Barn. On or about 10/1/2024, an employee was working on an energized 460 Volt AC electrical panel, without electrical protective equipment such as, but not limited to, gloves, and the employee received an electrical shock from a live part.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at NOVELIS CORPORATION
ATLANTA, GA—2023-10-05 00:00:00
NOVELIS CORPORATION
TERRE HAUTE, IN—2023-09-21 00:00:00
NOVELIS CORPORATION
TERRE HAUTE, IN—2023-03-06 00:00:00
NOVELIS CORPORATION
OSWEGO, NY—2019-11-20 00:00:00
NOVELIS CORPORATION
OSWEGO, NY—2018-12-27 00:00:00
NOVELIS CORPORATION
View NOVELIS CORPORATION's full OSHA safety record →
More inspections in this industry (NAICS 331318)
WHITES CREEK, TN—2026-05-26
TOTAL STRUCTURES, INC.
TIFTON, GA—2026-05-14
EXLABESA EXTRUSION TIFTON, INC.
GLEN DALE, WV—2026-04-16
TECNOCAP LLC
GOSHEN, IN—2026-04-15
PATRICK INDUSTRIES INC
PRINCE GEORGE, VA—2026-04-14
SCM INDUSTRIES, LLC
More inspections in NY
POUGHKEEPSIE, NY—2026-07-13
MARCO BOARD HOUSE, INC.
CORTLANDT MANOR, NY—2026-07-13
LG BUILDERS INC.
CORTLANDT MANOR, NY—2026-07-13
RJW RENOVATIONS, LLC
HEMPSTEAD, NY—2026-07-13
NYSDOCCS NASSAU AREA OFFICE
NIAGARA FALLS, NY—2026-07-10
NTVI FEDERAL INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347801995.