2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: HOLY CROSS HOSPITAL

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of HOLY CROSS HOSPITAL in 2701 W. 68TH STREET, CHICAGO, IL 60629 (NAICS 622110). OSHA activity number 347959355.

Watch Holy Cross Hospital — free Get an email when a new federal OSHA severe-injury report for Holy Cross Hospital is published. One employer, no account, unsubscribe in one click.
Establishment
HOLY CROSS HOSPITAL
Site address
2701 W. 68TH STREET
City
CHICAGO
State
IL
ZIP
60629
Mailing
2701 W. 68TH STREET, CHICAGO, IL 60629
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
583
Ownership type
A

2 citations on file for this inspection.

1910.219 D01

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $8500.00 Reduced
29 CFR 1910.219(d)(1): Guarding. Pulleys, any parts of which are seven (7) feet or less from the floor or working platform, was not guarded in accordance with the standards specified in paragraphs (m) and (o) of this section. Pulleys serving as balance wheels (e.g., punch presses) on which the point of contact between belt and pulley was not more than six feet six inches (6 ft. 6 in.) from the floor or platform may be guarded with a disk covering the spokes.  a. On or about December 30, 2025, the employer failed to ensure that the pulley assembly of the air handling unit, located at the elevator equipment room on the 6th floor of the S. Bldg. was fully guarded at points less than sever (7) feet from the floor. Thereby exposing employees to caught-in hazards.
Recent events (2)
  • — I (S) $8500
  • — Z (S) $16550

1910.219 E01 I

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.219(e)(1)(i): Where both runs of horizontal belts are seven (7) feet or less from  the floor level, the guard did not extend to at least fifteen (15) inches above the belt or to a standard height, except that where both runs of a horizontal belt are 42 inches or less from the floor, the belt shall be full enclosed in accordance with paragraphs (m) and (o) of this section.  a. On or about December 30, 2025, the employer failed to ensure that the horizontal belt and pulley assembly of the air handling unit, located at the elevator equipment room on the 6th floor of the S. Bldg. was fully guarded at points less than sever (7) feet from the floor.  Thereby exposing employees to caught-in hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View HOLY CROSS HOSPITAL's full OSHA safety record →