2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: POWER FLAME, INC

Federal Agency inspection · Health discipline

On , OSHA opened a federal Agency health inspection of POWER FLAME, INC in 2001 S 21ST ST, PARSONS, KS 67357 (NAICS 333994). OSHA activity number 347998841.

Watch Power Flame, INC — free Get an email when a new federal OSHA severe-injury report for Power Flame, INC is published. One employer, no account, unsubscribe in one click.
Establishment
POWER FLAME, INC
Site address
2001 S 21ST ST
City
PARSONS
State
KS
ZIP
67357
Mailing
2001 S 21ST ST, PARSONS, KS 67357
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333994
Employees
160
Ownership type
A

6 citations on file for this inspection.

1910.134 D01 III

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6384.00 · Current $4469.00 Reduced
29 CFR  1910.134(d)(1)(iii): The employer did not identify and evaluate the respiratory hazard(s) in the workplace; including a reasonable estimate of employee exposures to respiratory hazards and identification of the contaminant's chemical state and physical form:  On or about 01/24/2025, the employer had failed to conduct personal air sampling for employees in the powder coating areas. Employees powder coat metal parts with a variety of products, that includes Sky White powder coating and are equipped with supplied air respirators and tight-fitting air purifying respirators.
Recent events (2)
  • — I (S) $4468.8
  • — Z (S) $6384

1910.134 I05 I

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $8511.00 · Current $5958.00 Reduced
29 CFR  1910.134(i)(5)(i): Compressors used to supply breathing air to respirators were not so constructed and situated so as to prevent entry of contaminated air into the air-supply system:  Employees are exposed to respiratory health hazards. At the Southwest area of the building, the intake of the Sullair Industrial Air Compressor model no. 12BS-50H ACAC is located at the employee's parking lot, where vehicles back up next to the intake system and toxic exhaust gases could be pulled into the compressed air system and supplied air system.
Recent events (2)
  • — I (S) $5957.7
  • — Z (S) $8511

1910.134 I08

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $14895.00 · Current $10427.00 Reduced
29 CFR  1910.134(i)(8):An asphyxiating substance was introduced into breathing air lines:  On or about January 24, 2025, at the powder coat booth area, employee(s) were exposed to respiratory health hazards in that the installation of the three-way valve at the Trumpf laser, connecting the nitrogen and compressed air systems, allowed for possible the introduction of nitrogen gas into the breathing airlines used at the powder coat booth.
Recent events (2)
  • — I (S) $10426.5
  • — Z (S) $14895

1910.134 I01 II A

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.134(i)(1)(ii)(A): Breathing air did not contain 19.5-23.5% oxygen (volume/volume):    On or about January 24, 2025, at the powder coat booth area, employee(s) were exposed to respiratory health hazards in that the compressed air system did not meet requirements for Grade D breathing when oxygen levels dropped below 19.5%.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 H04 II

Other-than-serious 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.134(h)(4)(ii):Repairs were not made in accordance with the manufacturer's recommendations and specifications for the type and extent of repairs to be performed:  At the powder coat booth, employee(s) used the Allegro supplied-air hood which had a modification made on the waist belt assembly hose with a hose connection part that was not approved by Allegro.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 I05 IV

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.134(i)(5)(iv):The tag containing the most recent change to the sorbent beds was not maintained at the compressor:  At the southwest area of the building, the Sullair Air Compressor  model no. 12BS-50H ACAC did not have a tag showing most recent change date of the sorbent beds and the signature of the person authorized by the employer to perform the change.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View POWER FLAME, INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347998841.