Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: FORTIS SOLUTIONS GROUP, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FORTIS SOLUTIONS GROUP, LLC in 374 SOMERS ROAD, ELLINGTON, CT 06029 (NAICS 323111). OSHA activity number 348417775.

Watch Fortis Solutions Group, LLC — free Get an email when a new federal OSHA severe-injury report for Fortis Solutions Group, LLC is published. One employer, no account, unsubscribe in one click.
Site address
374 SOMERS ROAD
City
ELLINGTON
State
CT
ZIP
06029
Mailing
374 SOMERS ROAD, ELLINGTON, CT 06029
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323111
Employees
43
Ownership type
A

3 citations on file for this inspection.

1910.303 B07 IV

Serious Gravity 5 1 instance 4 exposed
Issued
Penalty
Initial $6833.00 · Current $4783.00 Reduced
29 CFR  1910.303(b)(7)(iv):  There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:  Warehouse:  On, or about, August 5, 2025, the cover provided on Challenger dock plate control panel was broken and ajar.
Recent events (2)
  • — I (S) $4783.1
  • — Z (S) $6833

1910.303 G01 I C

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(g)(1)(i)(C):  For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303.  Other equipment associated with the electrical installation and located above or below the electric equipment may extend not more than 153 mm (6 in.) beyond the front of the electric equipment:  Warehouse:  On, or about, August 5, 2025, a battery charging unit was installed in the working space of the Square D 120/208 volt Load Center.  The battery charging unit projected 13 inches beyond the face of the Load Center.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(g)(1)(ii):  The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Warehouse:  On, or about, August 5, 2025, hand trucks and brooms were stored in the working space for the Square D Load Center.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View FORTIS SOLUTIONS GROUP, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348417775.