ELLINGTON, CT —
OSHA Inspection: FORTIS SOLUTIONS GROUP, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FORTIS SOLUTIONS GROUP, LLC in 374 SOMERS ROAD, ELLINGTON, CT 06029 (NAICS 323111). OSHA activity number 348417775.
Where did this inspection happen?
- Establishment
- FORTIS SOLUTIONS GROUP, LLC
- Site address
- 374 SOMERS ROAD
- City
- ELLINGTON
- State
- CT
- ZIP
- 06029
- Mailing
- 374 SOMERS ROAD, ELLINGTON, CT 06029
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323111
- Employees
- 43
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 B07 IV
- Issued
- Penalty
- Initial $6833.00 · Current $4783.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: Warehouse: On, or about, August 5, 2025, the cover provided on Challenger dock plate control panel was broken and ajar.
Recent events (2)
- — I (S) $4783.1
- — Z (S) $6833
1910.303 G01 I C
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303. Other equipment associated with the electrical installation and located above or below the electric equipment may extend not more than 153 mm (6 in.) beyond the front of the electric equipment: Warehouse: On, or about, August 5, 2025, a battery charging unit was installed in the working space of the Square D 120/208 volt Load Center. The battery charging unit projected 13 inches beyond the face of the Load Center.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Warehouse: On, or about, August 5, 2025, hand trucks and brooms were stored in the working space for the Square D Load Center.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at FORTIS SOLUTIONS GROUP, LLC
VIRGINIA BEACH, VA—2024-01-04 00:00:00
FORTIS SOLUTIONS GROUP LLC
View FORTIS SOLUTIONS GROUP, LLC's full OSHA safety record →
More inspections in this industry (NAICS 323111)
MUSKEGON, MI—2026-07-08
GRAPHICS HOUSE PUBLISHING, INC
WARMINSTER, PA—2026-07-02
INNOTECH LASER
HERMITAGE, PA—2026-07-01
CCL CONTAINER, INC.
GREEN BAY, WI—2026-06-30
CHARTER NEXT GENERATION, INC.
LEHI, UT—2026-06-25
FIVE INC.
More inspections in CT
BRIDGEPORT, CT—2026-07-10
WRR, INC.
BERLIN, CT—2026-07-10
MMF CONSTRUCTION LLC
NAUGATUCK, CT—2026-07-08
WHITING-TURNER LCT2 JOINT VENTURE
SOMERS, CT—2026-07-08
F&G RECYCLING LLC
STAMFORD, CT—2026-07-07
FAIRFIELD AVENUE MAINTENANCE COMPANY, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348417775.