2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: ALTMAN SPECIALTY PLANT

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of ALTMAN SPECIALTY PLANT in 7960 CAGNON RD, SAN ANTONIO, TX 78252 (NAICS 424930). OSHA activity number 348478330.

Watch Altman Specialty Plant — free Get an email when a new federal OSHA severe-injury report for Altman Specialty Plant is published. One employer, no account, unsubscribe in one click.
Site address
7960 CAGNON RD
City
SAN ANTONIO
State
TX
ZIP
78252
Mailing
7960 CAGNON RD, SAN ANTONIO, TX 78252
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
424930
Employees
293
Ownership type
A

2 citations on file for this inspection.

1910.303 G02 I

Other-than-serious Gravity 5 3 instances 4 exposed
Issued
Penalty
Initial $8038.00 · Current $3215.00 Reduced
29 CFR  1910.303(g)(2)(i):Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i).  Instance A: On or about September 3, 2025, and at times prior thereto,  employees were exposed to live electrical wiring from an uncovered outlet; location: mechanic shop, office area.   Instance B: On or about September 3, 2025,  employees were exposed to live electrical wiring from an uncovered junction box; location: mechanic shop, back right bay.  Instance C:  On or about September 3, 2025,  employees were exposed to live electrical wiring from an uncovered light switch; location: mechanic shop, back right bay.
Recent events (3)
  • — F (O) $3215.2
  • — C (S) $8038
  • — Z (S) $8038

1910.334 A01

Other-than-serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $8038.00 · Current $3215.00 Reduced
29 CFR  1910.334(a)(1):Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation.  On or about September 3, 2025, employees were utilizing portable flexible cords that were hung in a fashion that could cause damage to the outer jacket or insulation.
Recent events (3)
  • — F (O) $3215.2
  • — C (S) $8038
  • — Z (S) $8038

View ALTMAN SPECIALTY PLANT's full OSHA safety record →