ASHLAND, MA —
OSHA Inspection: NYACOL NANO TECHNOLOGIES, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NYACOL NANO TECHNOLOGIES, INC. in 211 MEGUNKO ROAD, ASHLAND, MA 01721 (NAICS 325998). OSHA activity number 348651118.
Where did this inspection happen?
- Establishment
- NYACOL NANO TECHNOLOGIES, INC.
- Site address
- 211 MEGUNKO ROAD
- City
- ASHLAND
- State
- MA
- ZIP
- 01721
- Mailing
- 211 MEGUNKO ROAD, ASHLAND, MA 01721
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325998
- Employees
- 24
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.22 A01
- Issued
- Abate by
- Penalty
- Initial $3972.00 · Current $2780.00 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. Location - Sample lab and R&D lab. On or about 12/18/2025, the aisles and walkways in the lab spaces were not kept in an orderly condition to allow employees safe exit from the spaces in the event of an emergency.
Recent events (2)
- — I (S) $2780.4
- — Z (S) $3972
1910.28 B03 II
- Issued
- Abate by
- Penalty
- Initial $2838.00 · Current $1987.00 Reduced
General-duty citation text
29 CFR 1910.28(b)(3)(ii): The employer did not ensure that each employee be protected from tripping into or stepping into or through any hole that is less than 4 feet (1.2 m) above a lower level by covers or guardrail systems. Location - Main production area deck - In front of utility sink. On or about 12/18/2025, an open floor hole exposed employees to slip, trip, and fall hazards.
Recent events (2)
- — I (S) $1986.6
- — Z (S) $2838
1910.303 F01
- Issued
- Abate by
- Penalty
- Initial $2838.00 · Current $1987.00 Reduced
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:(a) Location - Sample lab. On or about 12/18/2025, the electrical switches on the panel in the sample lab were not marked or labeled to indicate their purpose.
Recent events (2)
- — I (S) $1986.6
- — Z (S) $2838
1910.304 F01 VIII
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits shall be listed and marked "SWD." Location - Sample lab. On or about 12/18/2025, the circuit breaker switch that controls the fluorescent lights in the sample lab were not listed and marked "SWD".
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B06
- Issued
- Abate by
- Penalty
- Initial $319.00 · Current $223.00 Reduced
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: Location - Front door in office building and door in QA/QC lab. On or about 12/18/2025, emergency exit signs were not illuminated so that in the event of an emergency, employees can find their way out of the facility.
Recent events (2)
- — I (O) $223.3
- — Z (O) $319
1910.178 L06
- Issued
- Abate by
- Penalty
- Initial $319.00 · Current $223.00 Reduced
General-duty citation text
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l): Location - Shipping / receiving and throughout. On or about 12/18/2025, written certification that a powered industrial truck (PIT) operator had been trained and evaluated in the operation of powered industrial trucks was not completed.
Recent events (2)
- — I (O) $223.3
- — Z (O) $319
More inspections in this industry (NAICS 325998)
CHARLOTTE, TX—2026-07-07
CLEMENTS FLUIDS
KINDRED, ND—2026-06-29
ICE CRYSTAL ENGINEERING
WAYNESVILLE, NC—2026-06-23
161409 - PREMIER MAGNESIA, LLC
SOUTH PLAINFIELD, NJ—2026-06-17
AVINTHIA INC
WARMINSTER, PA—2026-06-12
CRC INDUSTRIES, INCORPORATED
More inspections in MA
WORCESTER, MA—2026-07-10
QUINSIGAMOND COMMUNITY COLLEGE
FITCHBURG, MA—2026-07-10
KELLEY WOOD PRODUCTS, INC.
EVERETT, MA—2026-07-10
HORIZON RETAIL CONSTRUCTION INC
NORTON, MA—2026-07-09
DYNAMIC RESIDENTIAL ROOF MARKETING, LLC
NORTON, MA—2026-07-09
LM GENERAL CONSTRUCTION INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348651118.