PLACERVILLE, CA —
OSHA Inspection: USDA US FOREST SERVICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of USDA US FOREST SERVICE in 2480 CARSON ROAD, PLACERVILLE, CA 95667 (NAICS 113210). OSHA activity number 348654278.
Where did this inspection happen?
- Establishment
- USDA US FOREST SERVICE
- Site address
- 2480 CARSON ROAD
- City
- PLACERVILLE
- State
- CA
- ZIP
- 95667
- Mailing
- 2480 CARSON ROAD, PLACERVILLE, CA 95667
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 113210
- Employees
- 5
- Ownership type
- D
Citations
2 citations on file for this inspection.
1910.253 B04 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: At the Facility Maintenance Shop, on or around December 11, 2025, and at times before that date, the employer did not ensure that the oxygen and acetylene compressed gas cylinders were separated by a minimum distance of 20 feet, or by a noncombustible barrier at least 5 ft. high having a fire resistance rating of at least one hour. Employees were potentially exposed to fire hazards.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(2): Listed or�labeled electrical�equipment was�not used�or installed�in accordance�with instructions�included in�the listing�or labeling. Located inside the Bark Beetle Research building, on or about December 11, 2025, and at times prior thereto the employer did not ensure that a relocatable power tap was being used or installed in accordance with instructions included in the listing or labeling. A freezer (Thermo Scientific, model GT20LFEET8A) was energized by the relocatable power tap. Employees were exposed to burns from potential fire hazards.
Recent events (1)
- — Z (S) $0
More inspections at USDA US FOREST SERVICE
TOWNSEND, WI—2019-06-13 00:00:00
USDA US FOREST SERVICE
View USDA US FOREST SERVICE's full OSHA safety record →
More inspections in this industry (NAICS 113210)
MIDPINES, CA—2026-05-18
CA DEPARTMENT OF FORESTRY & FIRE PROTECTION (CAL FIRE)
WILLOW SPRINGS, MO—2026-03-25
U.S.D.A FOREST SERVICE
ORLANDO, FL—2026-03-10
GASTON TREE DEBRIS RECYCLING, L.L.C.
NIPOMO, CA—2025-12-19
CARL R HOLLOWAY OR DEBRA L HOLLOWAY, SOLE PROPRIETORSHIP
OLYMPIA, WA—2025-04-23
WA317985682 - IFA NURSERIES INC
More inspections in CA
IRVINE, CA—2026-07-13
SNEARY CONSTRUCTION, INC.
IRVINE, CA—2026-07-13
KUKBO DESIGN USA LLC
ENCINITAS, CA—2026-07-13
LOU RIDDLE CONSTRUCTION
CANYON COUNTRY, CA—2026-07-13
COLLEGE OF THE CANYONS
LINDSAY, CA—2026-07-13
NATIONAL DIVERSIFIED SALES, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348654278.