942,588Inspections Most recent open 2026-07-09 Last loaded 2026-07-13
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: NEXTIER COMPLETION SOLUTIONS INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of NEXTIER COMPLETION SOLUTIONS INC. in 31.884353 , -101.739508, GARDEN CITY, TX 79739 (NAICS 213112). OSHA activity number 348732447.

Site address
31.884353 , -101.739508
City
GARDEN CITY
State
TX
ZIP
79739
Mailing
3990 ROGERDALE, HOUSTON, TX 77042
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
213112
Employees
4
Ownership type
A

6 citations on file for this inspection.

19100132 F01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $16550.00
29 CFR  1910.132(f)(1)(i): The employer did not provide training to each employee who is required by this section to use PPE on knowing when PPE is necessary:  On or about December 16, 2025, at the E-Pump 650024 transformer room, employees were not adequately trained on when to use electrical protective equipment while working around a 13,800V fuse.
Recent events (1)
  • — Z (S) $16550

19100303 H02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $16550.00
29 CFR  1910.303(h)(2)(i): Electrical installations in a vault, room, or closet or in an area surrounded by a wall, screen, or fence, access to which is controlled by lock and key or other approved means, were not accessible to qualified persons only.  On or about December 16, 2025, at the E-Pump 650024 transformer room, the transformer room was not controlled to prevent accessibility to all but qualified persons.
Recent events (1)
  • — Z (S) $16550

19100333 B02 II B

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $16550.00
29 CFR  1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on were not disconnected from all electric energy sources:  On or about December 16, 2025, at the E-Pump 650024 transformer room, fuses were not disconnected from energy sources prior to employees performing troubleshooting operations.
Recent events (1)
  • — Z (S) $16550

19100333 B02 III A

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $16550.00
29 CFR  1910.333(b)(2)(iii)(A): A lock and a tag were not placed on each disconnecting means used to deenergize circuits and equipment on which work was to be performed:  On or about December 16, 2025, at the E-Pump 650024 transformer room, locks and tags were not used to deenergize circuits prior to employees performing troubleshooting operations.
Recent events (1)
  • — Z (S) $16550

19100333 B02 IV B

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $16550.00
29 CFR  1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts are deenergized:  On or about December 16, 2025, at the E-Pump 650024 transformer room, test equipment was not used to ensure that the transformer room and fuses were deenergized prior to employees performing troubleshooting operations.
Recent events (1)
  • — Z (S) $16550

19100335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $16550.00
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  On or about December 16, 2025, at the E-Pump 650024 transformer room, employees were not utilizing electrical protective equipment appropriate to protect against arc flashes and electrical shock while working around a 13,800V fuse.
Recent events (1)
  • — Z (S) $16550

View NEXTIER COMPLETION SOLUTIONS INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348732447.